HomeMy WebLinkAboutPlunketts, 40 52nd Way NE Remodel CITY OF FRIDLEY
FIRE DEPARTMENT
FIRE MARSHAL'S OFFICE
DEPARTMENT OF FIRE PREVENTION
Fire Department Building Plan Review
Date: August 15,2013
Address: Plunketts
40 52°a Way N.E. �
Fridley, MN 55432
Project: Remodel aa�., ' 13
BY•
Contractor: Unknown ,�
�''o
The conditions contained herein shall be considered as =e or the proposed project. A written
response or additional documents may be necessary and are due prior to completion of the Final
Inspection and approval for issuance of the Certificate of Occupancy or Fire Department permit
completion.You may contact the Office of the Fire Marshal at (763) 572-3621 for additional information.
1. Demolition and construction activities shall be governed by requirements of 2007 MSFC Chapter 14, Fire
Safety During Demolition and Construction, and NFPA Standard 241 (2000), Standard for Safeguarding
Construction,Alteration, and Demolition Operations.
2. Modify the fite sprinkler system as necessary compliant with provisions of 2002 NFPA Standard 13,
Installation of Sprinkler Systems, for alteration or construction work shown on reviewed plan. City FD
permit required prior to ixutiation of work. (2007 MSFC Sections 105.7.1, 901.4 and 2002 NFPA Standaxd
13)
a. The required sprinkler design density of the building fire sprinklex system shall include modification
for the proposed use of space or building. (2002 NFPA Standard 13)
3. Modification, alteration ox installation of a fire alarm system or equipment requires the fire alarm contractor
to apply for and receive a City of Fridley FD permit prior to initiation of work. A State of Minnesota
Electrical Permit may also be required through the City of Fridley Inspections Department. Required fire
alarm permit submittal docuxnents are provided in 2007 MSFC 907.1.1. (2007 MSFC 105.7.4)
4. Install emergency egress illumination in the means of egress including e�t discharge compliant with 2007
MSFC Section 1006,Means of Egress illumination.
5. Install compliant exit signage as required. (2007 MSFC Section 1011)
6. PYOVide and install dry chemical fire extinguishers certified for service as required. Service classification
rating shall be a minimum 2A classification rating and maxirnum travel distance of 75 feet to extinguishers.
The minimum classification rating may be upgraded for special or extra hazard areas within the occupancy.
(2007 MSFC Table 906.3(1).
a. Portable fire extinguishers shall also be installed in an unobscured,unobstnxcted location. If view of
fire extinguisher is obscured or obstructed, approved fire extinguisher signage shall be installed to
identify fire extinguisher locarion. (2007 MSFC 906.5 and 906.6)
b. When mounted in e�t passageways ox corridors, extinguisher mountings or cabinets shall not
obstnzct the egress path by moxe than 4 inches. (2007 MSFC Section 1003.3.3)
c. Fire extinguishers shall be installed so that the top of the extinguisher is not more than 60 inches
above the floor if 40 pounds or less gxoss weight. If the extinguisher has a gross weight exceeding
401bs, the extinguisheY shall be installed with the top not more than 3-1/2 feet above the floor. 'I'he
m;nimum distance above the floor shall be not less than 4 inches. (2007 MSFC 906.9)
•7. � Provide information concerning interior finish materials used for this project. Interior finish materials shall
be classified as required by 2007 MSFC Section 803 as to flame spread and smoke development
characteristics. Interior wall and ceiling finish shall have a flame spread index not greater than that specified
in 2007 MSFC Table 803.3 for the group of proposed occupancy and location of interior finish.
8. Inspect the unprotected space between the ceiling and roof deck and xemove all abandoned utilities,
combustible materials and storage from the unprotected space between the dropped ceiling and roof deck.
(2007 MSFC 102.8 and 304.1)
9. The required fire-resistance rating of rated construcrion shall be maintained. Openings through rated
construcrion for the passage of wiring, sleeves, conduit,piping, etc. shall be protected by repair with
approved materials which maintains the rating of the construcrion damaged, altered,breeched or penetrated.
(2007 MSFC 703.1)
10. Rooms contauung controls for air-conditioning systems, sprinkler risers and valves, or other fire detection,
suppression or control elements shall be idenrified for the use of the fire department. Approved signs
requixed to identify fixe pxotection equipment and equipment location, shall be constructed of durable
materials,pexmanendy installed and readily visible. (2007 MSFC 510.1)
11. Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating
"ELECTRICAL ROOM". The disconnecting means for each service, feeder or branch circuit originating
on a switchboard or panelboard shall be legibly and durably marked to indicate its purpose unless such
puxpose is clearly evident. (2007 MSFC 605.3.1)
12. Following completion of construction and approval of systems requiring Fire Department construction
permits,the Fire Maxshal will assist in a Certificate of Occupancy inspection. Please notify City Inspections
or the Fire Marshal Office for that inspection.
Reviewed by Matthew Field, Fire Marshal