HomeMy WebLinkAbout100618 FAlrmInspReportCITY OF FRIDLEY FIRE DEPARTMENT FIRE MARSHAL'S OFFICE DEPARTMENT OF FIRE PREVENTION Fire Alarm System Inspection Report NEW  EXISTING  MODIFICATION/UPGRADE  UL SYSTEM  BUILDING OWNER/BUSINESS: Springbrook Nature Center, City of Fridley INSPECTION SITE ADDRESS: 100 85th Av NE DATE OF INSPECTION: June 18, 2010 INSPECTION TYPE: Fire Alarm Install Test SYSTEM INFORMATION Annunciator in front lobby above pull station Fire alarm control panel is in sprinkler/mechanical room upstairs and has a half-door serving the room.       DEVIC ES TESTED Pull station in front lobby Smoke detector above FACP upstairs  Smoke detector in exhibit area Two horn strobes in exhibit area and assembly room  Annunciator in front lobby                                                SPRINKLER SYSTEM DEVICES TESTED Gate valve tamper # 1 Gate valve tamper # 2  Flow switch :52 sec (restricted flow into shower drain)         CORRECTIONS ORDERED None       SPECIAL STIPULATIONS (If any): None PERSONNEL TESTING SYSTEM: R Messer, Silent Knight technician, Siah St Clair COMMENTS: Keys for FACP and pull station in key box at front door.       Inspector: RM