HomeMy WebLinkAbout15-12-08 fire alarmCITY OF FRIDLEY FIRE DEPARTMENT FIRE MARSHAL'S OFFICE DEPARTMENT OF FIRE PREVENTION Fire Alarm Plan Review Comments Date: December 8, 2015 Address: 100 85th Avenue NW Project: Springbrook Nature Center Contractor: Life Safety Systems Contractor shall be familiar with this review document and contents prior to initiation of work. The conditions contained herein shall be considered as requirements for the proposed project. A written response or additional documents may be necessary and are due prior to initiation of the Final Inspection and approval for issuance of the Certificate of Occupancy or Fire Department permit completion. You may contact the Office of the Fire Marshal at (763) 572-3621 for additional information. Scope of this project: Call 763-572-3621 for all inspections/testing. General Comments: The proposed fire alarm system shall be installed in accordance with the 2007 Minnesota State Fire Code Section 907 and 2010 NFPA Standard 72, National Fire Alarm Code. A City of Fridley Inspections Department Electrical Permit may also be required for the proposed work. Smoke duct detection devices required for installation by the State Mechanical Code shall perform the intended function and generate a supervisory signal to the monitoring agency. (2007 MSFC 907.11.1.1) Duct detection device control/test units shall be located in approved visible, accessible location for building maintenance and/or Fire Department personnel. Control units shall be marked with labeling identifying the host heating, ventilation or air conditioning appliance. If the fire alarm control panel and/or fire service annunciator requires a code for access to silence and reset functions, the contractor shall install the City Fire Department code for those panel functions which is available from the Fire Marshal. If a key is required for access to silence and reset functions, the contractor shall be responsible for providing a key for the Fire Department key box. (2007 MSFC Section 506) When the silence function is activated at the fire alarm control panel or annunciator panel, audible notification function shall be silenced. The visual notification function (strobes) shall continue to operate until the system reset function is activated. (2007 MSFC 907.9.1) Monitoring agency shall report fire alarm incidents to the Fridley Fire Department’s dispatch center, Anoka County Central Communications, at (763) 427-1212. All devices shall be fully compatible with existing system components. Systems and their components shall also be listed and approved for the proposed purpose in the existing system. (2007 MSFC 907.1.2) Please forward information concerning device manufacturers, model numbers and listing information for these devices. Contractor may submit device cut sheets. (2007 MSFC 907.1.1.9) Testing of the System: Final inspection and testing of the installed system and monitoring signal generation shall be conducted in accordance with provisions of 2007 MSFC 907.17, 907.18 and 2002 NFPA Standard 72 and witnessed by the Fire Marshal. Contractor shall contact this office to arrange the witnessed testing and inspection. Contractor shall arrange for Central station monitoring agency to provide a list of signals which it receives during witnessed testing and inspection. A copy of this report shall be forwarded to this office. When permitted work, inspection and testing is completed, contractor shall provide the Fire Marshal’s office with a Certificate of Completion required by 2007 MSFC 907.18 and 2002 NFPA Standard 72 verifying that the system has been installed in accordance with approved plans and specifications. Reviewed by: Rick Current, Fire Marshal Fridley Fire Department Rick.current@fridleymn.gov