HomeMy WebLinkAboutSmith, Alex Letter SS VECTOR
E n G I n E E R S
VSE Project Number:U3507.0137.221
February 25,2022
TruNorth Solar LLC
ATTENTION: Donna Pickard
3735 Dunlap St.N.
Arden Hills,MN 55112
REFERENCE: Smith,Alex Residence: 5906 Benjamin Street Northeast,Fridley,MN 55432
Solar Array Installation
To Whom It May Concern:
Per your request, we have reviewed the existing structure at the above referenced site. The purpose of our review was to
determine the adequacy of the existing structure to support the proposed installation of solar panels on the roof as shown on
the panel layout plan.
Based upon our review,we conclude that the existing structure is adequate to support the proposed solar panel installation.
Design Parameters
Code: 2020 Minnesota Residential Code(2018 IRC)
Risk Category:II
Design wind speed,Vult: 115 mph(3-sec gust)
Wind exposure category: C
Ground snow load,Pg: 50 psf
Connection to Roof
Mounting connection: (1)5/16" lag screw w/min.2.5"threaded embedment into framing at max.48" o.c.along rails
Install(2)rails per row of panels,evenly spaced;panel length perpendicular to the rails shall not exceed 70 in
Rail cantilever shall not exceed 50%of connection spacing
Conclusions
Based upon our review, we conclude that the existing structure is adequate to support the proposed solar panel installation.
The glass surface of the solar panels allows for a lower slope factor per ASCE 7, resulting in reduced design snow load on
the panels. The gravity loads, and thus the stresses of the structural elements, in the area of the solar array are either
decreased or increased by no more than 5%. Stress decreases or increases of no more than 5% are considered acceptable.
Therefore,the structure is permitted to remain unaltered.
The solar array will be flush-mounted (no more than 10" above the roof surface) and parallel to the roof surface. Thus, we
conclude that any additional wind loading on the structure related to the addition of the proposed solar array is negligible.
The attached calculations verify the capacity of the connections of the solar array to the existing roof against wind (uplift),
the governing load case. Increases in lateral forces less than 10% are considered acceptable. Thus the existing lateral force
resisting system is permitted to remain unaltered.
651 W. Galena Park Blvd.,Ste. 101/Draper, UT 84020/T(801)990-1775/F(801)990-1776/www.vectorse.com
VSE Project Number: U3507.0137.221
Smith,Alex Residence
YE C T O R 2/25/2022
E M G I n E E R s
Limitations
Installation of the solar panels must be performed in accordance with manufacturer recommendations. All work performed
must be in accordance with accepted industry-wide methods and applicable safety standards. The contractor must notify
Vector Structural Engineering, LLC should any damage, deterioration or discrepancies between the as-built condition of the
structure and the condition described in this letter be found. Connections to existing roof framing must be staggered, except
at array ends, so as not to overload any existing structural member. The use of solar panel support span tables provided by
others is allowed only where the building type, site conditions, site-specific design parameters, and solar panel configuration
match the description of the span tables.The design of the solar panel racking(mounts,rails, etc.) and electrical engineering
is the responsibility of others. Waterproofing around the roof penetrations is the responsibility of others. Vector Structural
Engineering assumes no responsibility for improper installation of the solar array. Vector Structural Engineering shall be
notified of any changes from the approved layout prior to installation.
VECTOR STRUCTURAL ENGINEERING,LLC
LICENSED
m PROFESSIONAL
ENGINEER —
02/25/2022
Brett Veazie,P.E. I hereby certify that this plan,specification or report
Project Engineer was prepared by me or under my direct supervision
and that I am a duly Licensed Professional Engineer
under the laws of the State of Minnesota,
Enclosures Brett D.Veazie, License No.56392,
Expiration Date:30-June-2022
BDV/rsl
651 W. Galena Park Blvd.,Ste. 101/Draper, UT 84020/T(801)990-1775/F(801)990-1776/www.vectorse.com
JOB NO.: U3507.0137.221
YETO R SUBJECT: WIND PRESSURE
n G 1 n E E R S
PROJECT: Smith, Alex Residence
Com onents and Cladding Wind Calculations
Label: ISolar Panel Array Note: Calculations per ASCE 7-10
SITE-SPECIFIC WIND PARAMETERS:
Basic Wind Speed [mph]: 115 Notes:
Exposure Category: C
Risk Category: II
ADDITIONAL INPUT & CALCULATIONS:
Height of Roof, h [ft]: 15 (Approximate)
Comp/Cladding Location: Gable Roofs 27°< 0 <_45°
Enclosure Classification: Enclosed Buildings
Zone 1 GCp: 1.0 Figure 30.4-2C (enter negative pressure coefficients)
Zone 2 GCp: 1.2
Zone 3 GCp: 1.2
a: 9.5 Table 26.9-1
z9 [ft]: 900 Table 26.9-1
Kh: 0.85 Table 30.3-1
KZt: 1 Equation 26.8-1
Kd: 0.85 Table 26.6-1
Velocity Pressure, qh [psf]: 24.4 Equation 30.3-1
GCp;: 0 Table 26.11-1
PRESSURES: p = q, GCp — GCpi Equation 30.9-1
Zone 1, p [psf]: 24.1 psf (1.0 W, Interior Zones, beyond 'a' from roof edge)
Zone 2, p [psf]: 29.0 psf (1.0 W, End Zones, within 'a' from roof edge)
Zone 3, p [psf]: 29.0 psf (1.0 W, Corner Zones, within 'a' from roof corner)
(a= 3 ft)
JOB NO.: U3507.0137.221
YETO R SUBJECT: CONNECTION
n G In E E R S
PROJECT: Smith, Alex Residence
Calculate Uplift Forces on Connection
Pressure Max Trib. Width 1 2 Max Trib. Max Uplift
(0.6 Dead -0.6 Wind) Area Force
(psf) (ft) (ft2) (Ibs)
Zone 1 12.7 4.0 11.7 148
Zone 2 15.6 4.0 11.7 182
Zone 3 15.6 4.0 11.7 182
Calculate Connection Capacity
Lag Screw Size [in]: 5/16
Cd: 1.6 NDS Table 2.3.2
Embedment3 [in]: 2.5
Grade: SPF (G = 0.42)
Nominal Capacity [Ibs/in]: 205 NDS Table 12.2A
Number of Screws: 1
Prying Coefficient: 1.4
Total Capacity [Ibs]: 586
Determine Result
Maximum Demand [lbs]:l 182
Lag Screw Capacity [lbs]:1 586
Result: Capacity > Demand, Connection is adequate.
Notes
1. 'Max Trib. Width' is the width along the rails tributary to the connection.
2. 'Max Trib Area' is the product of the 'Max.Trib Width' and 1/2 the panel width/height perpendicular to the
rails. (2) rails per row of panels. Length of panels perpendicular to the rails shall not exceed 70".
3. Embedment is measured from the top of the framing member to the beginning of the tapered tip of the lag
screw. Embedment in sheathing or other material is not effective.The length of the tapered tip is not part of the
embedment length.
JOB NO.: U3507.0137.221
YET O R SUBJECT: GRAVITY LOADS
n G I n E E R S
PROJECT: Smith, Alex Residence
GRAVITY LOADS Roof Pitch: 7.0 :12
Design material Increase due to Material weight
ROOF DEAD LOAD (D) weight [psf] pitch [psf]
Composite Shingles 2.3 1.16 2.0
1/2" Plywood 1.2 1.16 1.0
Framing 3.0 3.0
Insulation 0.5 0.5
1/2" Gypsum Clg. 2.3 1.16 2.0
M, E & Misc 1.5 1.5
Total Existing Roof DL 10.8
PV Array DL 3.5 1.16 3
ROOF LIVE LOAD (Lr)
Existing Design Roof Live Load [psf] 20 ASCE 7-10 Table 4.3-1
Roof Live Load With PV Array [psf] 0 2020 MRC, Section R324.4.1.1
SNOW LOAD (S): Existing w/ Solar Array
Roof Slope [x:12]: 7.0 7.0
Roof Slope [°]: 30 30
Ground Snow Load, pg [psf]: 50 50 ASCE 7-16, Section 7.2
Terrain Category: C C ASCE 7-16, Table 7.3-1
Exposure of Roof: Fully Exposed Fully Exposed ASCE 7-16, Table 7.3-1
Exposure Factor, Ce: 0.9 0.9 ASCE 7-16, Table 7.3-1
Thermal Factor, Ct: 1.1 1.1 ASCE 7-16, Table 7.3-2
Risk Category: 11 II ASCE 7-16, Table 1.5-1
Importance Factor, Is: 1.0 1.0 ASCE 7-16, Table 1.5-2
Flat Roof Snow Load, pf [psf]: 35 35 ASCE 7-16, Equation 7.3-1
Minimum Roof Snow Load, pm [psf]: 0 0 ASCE 7-16, Section 7.3.4
Unobstructed Slippery Surface? No Yes ASCE 7-16, Section 7.4
Slope Factor Figure: Figure 7-2b Figure 7-2b ASCE 7-16, Section 7.4
Roof Slope Factor, Cs: 1.00 0.66 ASCE 7-16, Figure 7.4-1
Sloped Roof Snow Load, Ps [psf]: 35 23 ASCE 7-16, Equation 7.4-1
Design Snow Load, S [psf]: 35 23
JOB NO.: U3507.0137.221
TO R SUBJECT: LOAD COMPARISON
E n G I n E E R S
PROJECT: Smith, Alex Residence
Summary of Loads
Existing With PV Array
D [psf] 11 14
Lr [psf] 20 0
S [psf] 35 23
Maximum Gravity Loads:
Existing With PV Array
(D+ Lr)/Cd [psf] 25 16 ASCE 7-10, Section 2.4.1
(D +S)/Cd [psf] 40 32 �ASCE 7-10, Section 2.4.1
(Cd=Load Duration Factor=0.9 for D,1.15 for S,and 1.25 for Lr)
Maximum Gravity Load [psf]:1 40 1 32
Ratio Proposed Loading to Current Loading: 1 82% OK
The gravity loads, and thus the stresses of the structural elements, in the area of the
solar array are either decreased or increased by no more than 5%. Stress decreases or
increases of no more than 5%are considered acceptable.Therefore,the structure is
permitted to remain unaltered.
JOB NO.: U3507.0137.221
yT O R SUBJECT: SOLAR LAYOUT
n G I n E E R S
PROJECT: Smith, Alex Residence
'f PLANVIEW AREA IS 2609 SQUARE FT
ARRAY AREA 814 SQUARE FT _
►. ARRAY IS 31% OF PLANVIEW AREA
- 18" Setback from ridge
36" Pathway to ridge ..'
lot-
:'r,<71
L 4b