HomeMy WebLinkAboutElectric One Line and SchedulesREV01_144Bxx - Smith, Alex (1) INVERTERS(SOLAREDGE) r 65...............
(1)SE11400H-US,11400W INTERNET
24OV,47.5A,10 Network Communication to ACCESS
10 0 10 TOTAL:11.4KW AC,47.5A 1 Customer Owned Router •............••••.
oc oc ; UL 1741 CERTIFIED
0 D 1
' 1
CONDUCTORSAND ��� 1 SERVICE PANEL 80....... ......""
JBOXTYPIIFAL 1 SIEMENS
•' :
13.., 40 ••••••••••••••• 46 240VAC,150A,10
4 5 �� ac 4 OCP:150A -- —___
L L ..r
DC
INVERTER 1
ti..................
0 10
DC EXT. NORTH SIDE OF HOUSE INTERIOR
i ROOFTOP
5............f.......................... ...............
UTILITY AC DISCONNECT MAIN METER '
VISIBLE-OPEN TYPE UTLITY OWNED
LOCKABLE,NEMA 3R BIDIRECTIONAL
READILY ACCESSIBLE 240V,200A,10,3-WIRE
SERVICE RATED DIRECT MEASURE I
60A,240VAC,2-POLE
FUSING OPTIONAL:60A
DC-DC OPTIMIZERS:(SOLAREDGE)
PV MODULES (37)SE P401,40OW
Q-Cells 1 MOD.PER OPTIMIZER
(37) Q.PEAK DUO BLK ML-10+395 REQUIREMENTS EACH STR: r I
STC:395,MPV:36.88,MPI:10.71 PV MAX 6000W r
VOC:45.72,ISC:11.1 8-15 PV MODULES r�
TOTAL:14.615KW DC 8-25 OPTIMZERS 71
93........ .....:
3 STR PER INV 1:(PV 15,11,11) RPA (Reference Point of Applicability): 62 SPD 85
PoC(Point of DER Connection) :
LOCATED AT INVERTER CONNECTION IVI '
IT
94
ANTI-ISLANDING TEST POINT 72 M
•�i 73 90 '
_...........
__ ----
PRODUCTION METER ___ _ — ''""""'
DISCONNECT I
GENERAL NOTES: 60A,240VAC,2-POLE SYSTEM TIE-IN(TAG 90)
FUSED:60A MFG PROVIDED '
--DESIGN MEETS ALL NEC REQUIREMENTS UL LISTED,75'C.
--GROUNDING CONDUCTORS MAY NOT BE SHOWN MIN.RATING:60A
--REFER TO ELECTRICAL LABEL SCHEDULE(DWG E2 BELOW)FOR DETAILED LABEL INFO METER TAP KIT
--EQUIPMENT AND WIRE/CONDUIT SCHEDULES FOLLOW(DWG E3&E4 BELOW)
--RAPID SHUTDOWN IS INITIATED BY AC DISCONNECT OR INTEGRATED INVERTER SWITCH
MISC.NOTES AND SPECS:
TAG
0 PV MODULE 1: (QUANTITY 37) STC:395;MPV:36.88;MPI:10.71;VOC:45.72;ISC:11.1 DISCONNECT TO MAIN METER:4'
1 PV MODULE 2: N/A ♦—————————————————♦
40 INVERTER 1 (QUANTITY 1) 240V;11,400W;47.5A;10;UL 1741 CERTIFIED 99 I EXT. NORTH SIDE OF HOUSE
41 INVERTER: N/A
--INVERTER(S)ARE 240VAC 10 OUTPUT
--SYSTEM OUTPUT IS BALANCED 240VAC 10
ELECTRICAL ONE-LINE DIAGRAM
CUST: ALEX N SMITH (989)854-2748 ELECT.UTILITY: XCEL ENERGY E1: REV 01
3735 Dunlap Street N SITE: 5906 Benjamin St,Fridley,MN 55432 PREMISE#: 302978818 EDIT:BF
TruNorth Solar Arden Hills,MN 55112 SERVICE: 120/240V,10,3-WIRE,150A ACCOUNT#: 51-0011474124-6 2/16/2022
612-888-9599 PROJ: Smith,Alex METER#: 27693869 NOT FOR CONSTRUCTION UNLESS
SIZE: 14.615KW DC 11.4KW AC APP ID#: 04793927 SOLAR REWARDS APPROVED BY MASTER ELECTRICIAN
LABEL SCHEDULE
ALL LABELS ARE DURABLE,PERMANENT AND NEC 690 COMPLIANT.EXTERIOR LABELS ARE WEATHERPROOF. ORANGE FILL COLOR INDICATES THE LABEL IS REQUIRED
EXACT LABEL TEXT AND FORMAT MAY VARY IF MEANING IS CLEAR AND MEETS CODE REQUI9REMENTS. LT YELLOW: INDICATES THE LABEL NORMALLY APPLIED TO EQUIPT BY MFG
COLOR SHOWN HERE INDICATES WHETHER LABEL APPLIES,NOT PHYSICAL LABEL COLOR. WHITE/NO COLOR: INDICATES THE LABEL DOES NOT APPLY(IGNORE)
APPLY: MAIN METER APPLY: AC DISCO,PROD METER,COMBINER,AUX TRANSFORMER APPLY: PV SOURCE RACEWAYS,J-BOX COVERS,ETC.
Ill 906 MAIN(BIDIRECTIONAL)METER 497 WARNING: ELECTRIC SHOCK HAZARD-DO NOT 31 904 (SM) WARNING: PHOTOVOLTAIC POWER SOURCE
TOUCH TERMINALS-LINE AND LOAD TERMINALS 905 (MED) WARNING: PHOTOVOLTAIC POWER SOURCE
APPLY: MAIN METER,MAIN PANEL MAY BE ENERGIZED IN THE OPEN POSITION 910 (LG) WARNING: PHOTOVOLTAIC POWER SOURCE
2 HT ROL WARNING: DUAL POWER SOURCES,
SECOND SOURCE IS PV SYSTEM APPLY: METER COMBO,AC COMBINER,TAP CAN APPLY: INVERTER(DC DISCONNECT)
1 499 WARNING:TURN OFF PHOTOVOLTAIC AC DISCONNECT 999 INVERTER 1,INVERTER 2...ETC.
APPLY: PRODUCTION METER PRIOR TO WORKING INSIDE PANEL 1 SOLAR DC DISCONNECT
Ill 909 SOLAR PRODUCTION METER MAXIMUM DC VOLTAGE 480.0 V
APPLY: AC DISCO(SOLAR SIDE OF TRANSFORMER)
APPLY: UTILITY AC DISCONNECT 1 999 PRODUCTION METER DISCONNECT APPLY: INVERTER(DC DISCONNECT)
1 HT ROLL RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM 239 PHOTOVOLTAIC AC DISCONNECT 999 INVERTER 1
1 999 UTILITY PHOTOVOLTAIC MAIN AC DISCONNECT MAX AC OPERATING CURRENT: 47.5 A SOLAR DC DISCONNECT
Ill 239 PHOTOVOLTAIC AC DISCONNECT OPERATING AC VOLTAGE: 240 VAC 1(d MAXIMUM DC VOLTAGE V
MAX AC OPERATING CURRENT: 47.5 A
OPERATING AC VOLTAGE: 240 VAC 10 APPLY: SOLAR AC COMBINER PANEL APPLY: (MISC.DC DISCONNECT)
1 JHT ROL SOLAR PV SYSTEM EQUIPPED 1 WARNING: SOLAR CIRCUITS ONLY 999 SOLAR DC DISCONNECT
WITH RAPID SHUTDOWN DO NOT ADD OTHER LOADS! SOLAR DC DISCONNECT
MAXIMUM DC VOLTAGE V
�pOvm wSMiEM
4=1 APPLY: EXT.MAIN METER SERVICE PANEL APPLY: SOLAR AC COMBINER PANEL 1
705 WARNING:THIS EQUIPMENT FED BY MULTIPLE SOURCES 999 SOLAR COMBINER PANEL
TOTAL RATING OF ALL OVERCURRENT DEVICES 239 PHOTOVOLTAIC AC DISCONNECT
APPLY: SOLAR&UTILITY SERVICE EQUIPMENT EXCLUDING MAIN SUPPLY OVERCURRENT DEVICE MAX AC OPERATING CURRENT: 47.5 A
121 CUST. CAUTION:MULTIPLE SOURCES OF POWER SHALL NOT EXCEED AMPACITY OF BUSBAR OPERATING AC VOLTAGE: 240 VAC 10
(FIELD) INPUT CIRCUIT NAME OP.VOLTAGE. OP.CUR.
TO BE CREATED:SITE SPECIFIC DIAGRAM SHOWING APPLY: EXT.SERVICE DISCONNECT 1 INV 1 VAC A
LOCATIONS OF ASSOCIATED EQUIPMENT SUCH AS:
MAIN METER 1 EMERGENCY DISCONNECT, 2 INV 2 240 VAC 47.5 A
UTILITY SERVICE DISCO SERVICE DISCONNECT 3 INV 3 240 VAC 47.5 A
SOLAR AC DISCO 4 VAC A
PRODUCTION METER APPLY: ESS BATTERIES 5 VAC A
INVERTERS,COMBINERS,LOCAL DISCOS AS NEEDED ENERGY STORAGE SYSTEM DISCONNECT 6 VAC A
SOLAR PV ARRAYS
MAXIMUM DC VOLTAGE:400V
BATTERIES,STANDBY GENERATOR(AS NEEDED)
INCLUDES ORIENTATION OF NORTH APPLY: SOLAR AC COMBINER PANEL
LL APPLY: MISC. 999 SOLAR COMBINER PANEL nn
UTILITY METER#2(CUST.SELL) 239 PHOTOVOLTAIC AC DISCONNECT
APPLY: BACKFED BREAKER IN SERVICE PANEL MAX AC OPERATING CURRENT: A
HT ROL WARNING: INVERTER OUTPUT CONNECTION APPLY: MISC. OPERATING AC VOLTAGE: VAC 10
DO NOT RELOCATE THIS OVERCURRENT DEVICE (FIELD) INPUT CIRCUIT NAME OP.VOLTAGE. OP.CUR.
1 VAC A
APPLY: MISC. 2 VAC A
APPLY: MAIN METER OR UTILITY SERVICE AREA 3 VAC A
1 RUNORTH SOLAR 4 VAC A
612-888-9599 APPLY: MISC. 5 VAC A
WWW.TRUNORTHSOLAR.COM 9 1 1 1 6 VAC A
ELECTRICAL LABEL SCHEDULE
CUST: ALEX N SMITH (989)854-2748 ELECTRIC UTILITI XCEL ENERGY E2: REV 01
3735 Dunlap Street N SITE: 5906 Benjamin St, Fridley, MN 55432 PREMISE#: 302978818 EDIT: BF
TruNorth Solar Arden Hills, MN 55112 SERVICE: 120/240V, 10,3-WIRE, 150A ACCOUNT#: 51-0011474124-6 2/16/2022
612-888-9599 PROJ: Smith,Alex METER#: 27693869 NOT FOR CONSTRUCTION UNLESS
SIZE: 14.615KW DC 11AKW AC APP ID#: 04793927 APPROVED BY MASTER ELECTRICIAN
O EQUIPMENT SCHEDULE
DC EQUIPMENT
TAG QUANT DESCRIPTION OR ID MFG PART# SPECS NOTES
0 37 MODULE 1 Q-Cells Q.PEAK DUO BLK ML STC:395;MPV:36.88;MPI: 10.71;VOC:45.72;ISC:
1
2
10 37 DC-DC OPTIMIZER SOLAREDGE P401 400W; 1 PV MODULE PER OPTIMIZER
11
13 1 1 JBOX(SOLAR) SOLADECK/OTHER JNEMA3R AS NEEDED FOR WIRE TRANSITIONS,MAY NOT BE SHOWN
14
15
16
17
INVERTERS
40 1 INVERTER 1 ISCLAREDGE SE1140OH-US 240V; 11,400W;47.5A; 10; UL 1741 EXT.METER AREA
41
42
43
AC EQUIPMENT
46 1 INV.COMMUNICATIONS KIT SOLAREDGE 1 FOR WIRELESS OR HARDWIRE,1 EACH INVERTER IF CELLULAR
47
50
51
52
53
54
60
61
62 2 SPD-SURGE PROTECTIVE DEVICE DELTA OR SIMILAR LA302 TYPES 1&2 SOLAR SERVICE,UTILITY SERVICE
63
65 1 INTERNET ROUTER MONITORING DATA ACCESS TO INTERNET CUSTOMER OWNED
66
67
68
70 1 UTILITY AC DISCO SQUARE-D OR SIM. DU222RB 240VAC,60A,2-POLE,UNFUSED,NEMA3R,SVC RATED EXT.METER AREA
71 2 UTILITY AC DISCO FUSE 60A 250VAC
72 1 PRODUCTION METER DISCONNECT SQUARE-D OR SIM. D222NRB 240VAC,60A,2-POLE,FUSED,NEMA3R,SVC RATED
73
74
80 1 SERVICE PANEL SIEMENS 240VAC,150A,10
81
82
84 1 PRODUCTION METER SOCKET MILBANK OR SIMILA U4801-XL-5T9 600V,200A,10,3-WIRE,BYPASS,NEMA3R EXT.METER AREA
85 1 PRODUCTION METER UTILITY OWNED ONE-WAY 240V,200A,10,3-WIRE
86
87
90 1 SYSTEM TIE-IN HARDWARE MILBANK K4977-EXT UL,300V,100A TAP CONNECTOR KIT MFG PROVIDED
91
92
93 1 MAIN METER SOCKET IMILBANK OR SIMILA U4801-XL-5T9 160OV,200A,10,3-WIRE,BYPASS,NEMA3R
94 1 MAIN UTILITY METER JUTLITY OWNED JBIDIRECTIONAL 1240V,200A,10,3-WIRE
95
96
99 1 UTLITY TRANSFORMER UTILITY OWNED
3735 Dunlap Street N ELECTRICAL EQUIPMENT SCHEDULE E3: REV 01
TruNorth Solar Arden Hills, MN 55112 Smith,Alex CUST: ALEX N SMITH (989)854-2748 EDIT: BF
612-888-9599 14.615KW DC 11AKW AC SITE: 5906 Benjamin St, Fridley, MN 55432 2/16/2022
WIRE AND CONDUIT SCHEDULE
DC CIRCUITS
CIRCUIT MI SIZE CONDUIT
1-WAY #WIRES MIN.
TAG QUANT. DC CIRCUIT OR SEGMENT NAME WIRE TYPE SIZE LEN. EACH TYPE CONDUIT NOTES
(FT) CIRCUIT SIZE
0 37 PV MODULE 1 OUTPUT PV 12 AWG 4 2 (NOT SHOWN)PV MODULE LEADS
1
2
4 3 DC CONDUCTOR(FREE AIR) CU-PVWIRE 10 AWG 70 2 OPTIMIZER DC CIRCUITS TO JBOX
5 3 DC CONDUCTOR CU-THWN2 12 AWG 50 2 EMT 0.75" JBOX OUTPUT TO INVERTER
6
7
8
10
11
12
13
14
15
AC CIRCUITS
CIRCUIT MI SIZE CONDUIT
1-WAY #WIRES MIN.
TAG QUANT. AC CIRCUIT OR SEGMENT NAME WIRE TYPE SIZE LEN. EACH TYPE CONDUIT NOTES
(FT) CIRCUIT SIZE
40 1 INVERTER 1 CU-THWN2 6 AWG 6 2+N,G EMT 0.75" OUTPUT TO AC DISCO
41
42
50
51
52
53
68
70
71 1 UTILITY AC DISCO CU-THWN2 6 AWG 6 2+N,G EMT 0.75" TO PRODUCTION METER
72 1 PRODUCTION METER CU-THWN2 6 AWG 6 2+N,G EMT 0.75" TO PRODUCTION METER DISCONNECT
73 1 PRODUCTION METER DISCONNECT CU-THWN2 6 AWG 6 2+N,G EMT 0.75" TO SYSTEM TIE-IN POINT(TAG 90)
91
101
102 1 EGC CU 6 AWG 100 1 10 AWG ALLOWED WHERE PROTECTED
103 1 AUX.GROUNDING ELECTRODE&CONDUCTC CU AS NEEDED PER NEC 690.47,FOR DC: 250.166;FOR AC:TABLE 250.66
104
WIRE&CONDUIT SCHEDULE E4: REV 01
3735 Dunlap Street N EDIT: BF
TruNorth Solar Arden Hills, MN 55112 Smith,Alex CUST: ALEX N SMITH (989)854-2748 2/16/2022
612-888-9599 14.615KW DC 11AKW AC SITE: 5906 Benjamin St, Fridley, MN 55432 NOT FOR CONSTRUCTION UNLESS
APPROVED BY MASTER ELECTRICIAN
CONDUCTOR SIZING CALCULATIONS
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
J z .ti N Ul ry _ K _
F w w F Q w z d' d' U- Z !n !n Q F O w F w Z
Z d' W U 2' F d' Z W w J .-i w U.
N w °� Z w w W N ..
Q O .~W. W d' F F O Z O w F > K F Z W O !n N .-i W J � F F W
F Ur !n Z U Z F W F F > d' O Q O Q , w 0 Z LL !n
Ua w Q uWi Ow � w U � U Q DOS � � ZUO DUpj � Upj in � g � CD w � �
F CIRCUIT OR SEGMENT NAME a J Q u o z w a U O w m w F Z F w Z F w F z � F z = 0 LL
0 N O a OU QU � � w � Qw xk of 0 � O Q � pUOQ 0 � � 0 � � � ��� zwF Lf' z �taii
U N z izF LLF O Dv D" a Of J
U U
4 3 DC CONDUCTOR(FREE AIR) _CU-PVWIRE 10 AWG 400 1 14.8 15 140 0.71 0 1 0.71 18.8 21.1 16 AWG ITABLE 310.17(FREE AIR) 70 0.64%
5 3 DC CONDUCTOR CU-THWN2 12 AWG 400 1 14.8 15 86 1 2 1 1 18.8 15 14 AWG TABLE 310.16 50 0.73%
6
40 1 INVERTER 1 CU-THWN2 6 AWG 240 1 47.5 47.5 86 1 2 1 1 59.4 47.5 6 AWG TABLE 310.16 6 0.12%
41
42
50
51
68
70
71 1 UTILITY AC DISCO CU-THWN2 6 AWG 240 1 47.5 47.5 86 1 2 1 1 59.4 47.5 6 AWG TABLE 310.16 6 0.12%
72 1 PRODUCTION METER CU-THWN2 6 AWG 240 1 47.5 47.5 86 1 2 1 1 59.4 47.5 6 AWG TABLE 310.16 6 0.12%
73 1 PRODUCTION METER DISCONNECT CU-THWN2 6 AWG 240 1 47.5 47.5 50 1.15 3 1 1.15 59.4 1 41.3 6 AWG 6 0.12%
NOTES FOR INDICATED COLUMN:
5 WIRE SIZE SPECIFIED IN ONE-LINE TYPICALLY INCLUDES CONSIDERATION FOR VOLTAGE DROP AND CONNECTION TERMINAL/LUG REQUIREMENTS
8 FOR DC OPTIMIZER STRING: (SUM OF PV WATTAGE)/(DC VOLTAGE REQUIRED BY INVERTER).FOR AC CIRCUITS,TYPICALLY INVERTER OUTPUT RATING
9 PV CIRCUITS=COLUMN 8*1.25.OPTIMIZER CIRCUITS= MAXIMUM CONTINUOUS OPTIMIZER OUTPUT RATING.INVERTER OUTPUT CIRCUIT= INVERTER CONTINUOUS RATING.
10 TEMPERATURE OF CONDUCTOR ENVIROMENT(FAHRENHEIT)
11 TEMPERATURE CORRECTION FACTOR FROM TABLE 310.15(B)(1)
12 QUANTITY OF CURRENT CARRYING CONDUCTORS IN THE CONDUIT
13 FROM TABLE 310.15(C)(1)
14 COMBINE ADJUSTMENTS AND CORRECTION FACTORS,COLUMN 11*COLUMN 13
15 TEST#1 =COLUMN 9*1.25--NEC 690.8(B)(1),MAXIMUM CIRCUIT CURRENT*1.25.THIS IS ALSO THE VALUE USED FOR OCP SIZING.
16 TEST#2=COLUMN 9/COLUMN 14--NEC 690.8(B)(2),MAX.CIRCUIT CURRENT WITH ADJUSTMENTS AND CORRECTION FACTORS
17 FROM TABLE 310.16 OR 310.17.LARGEST SIZE RESULTING FROM CALCULATIONS IN COLUMNS 15&16
18 NEC TABLE REFERENCED
19 ONE WAY LENGTH.NOTE THIS IS ONLY FOR THE SEGMENT SPECIFIED.ADDITIONAL SEGMENTS WILL ADD TO THE TOTAL VOLTAGE DROP OF A CIRCUIT.
20 VOLTAGE DROP PERCENTAGE USING THE OPERATING VOLTAGE AND NOMINAL CURRENT FOR THE SEGMENT
CONDUCTOR SIZING CALCULATIONS E5: REV 01
3735 Dunlap Street N EDIT: BF
TruNorth Solar Arden Hills, MN 55112 Smith,Alex CUST: ALEX N SMITH 2/16/2022
612-888-9599 14.615KW DC 11AKW AC SITE: 5906 Benjamin St, Fridley, MN 55432 NOT FOR CONSTRUCTION UNLESS
APPROVED BY MASTER ELECTRICIAN