HomeMy WebLinkAboutStamped Permit Set About the NEP BDM-300X2
As the NEP BDM-300X2 Microinverter we are using is likely unfamiliar to the majority of plan
reviewers, here is a brief explanation of some of the particulars of how this piece of equipment
fits into our plan sets:
1. The NEP BDM-300X2 is intended to be connected with 2 solar modules (solar panels)
per each 1 microinverter. If there is an odd number of solar modules, we are able to have
one microinverter with only one panel connected to it.
2. The rated AC output power of this microinverter is 500 watts. Some of you may have
specs sheets stating that it is 510. This is based on an out-of-date model. The
manufacturer has confirmed that the output power is 500 and has provided us with specs
sheets confirming this.
3. The AC system size is to be calculated by multiplying the number of microinverters by
the rated AC output power (500). AC system size should NOT be calculated by
multiplying the number of microinverters by the peak AC output power (580), as that
would be incorrect.
4. The NEP BDM-300X2 does not require a combiner panel unless there is more than one
circuit of microinverters being installed. The only exception to this is found in "5", below:
5. The NEP BDM-300X2 requires the addition of a monitoring system. This monitoring
system would ideally be installed in the Main Service Panel via a 15A-2P breaker. If
there is not space in the Main Service Panel to install this breaker in addition to our solar
interconnection, we will install a combiner panel in order to be able to install this breaker
as close as possible to the point of interconnection.
SHEET INDEX SCOPE OF WORK STREET VIEW GE VIEW SOICIU
PV01 TITLE SHEET Installation of Solar PV System
PV02 SITE PLAN
#OF PANELS: 20 r.
PV03 ELECTRICAL LINE DIAGRAM #OF INVERTERS: 10 - REGIONALOFFICE:
PV04 EQUIPMENT LABELS SOLCIUS, LLC
PV05 ATTACHMENTSPACING DC SYSTEM SIZE: 7.4 KW-DC 9124GRANDAVE
PV06 RACK RAIL DIAGRAM AC SYSTEM SIZE: 5 KW-AC S SUITE 105
SPECIFICATION SHEETS MINNEAPOLIS,
Latitude Longitude 1 MN 55420
45.067198 -93.231664 )
844 357-2258
APPLICABLE CODES CONSTRUCTION NOTES CUSTOMER:
2017 NATIONAL ELECTRIC CODE (NEC) A. ALL GROUNDING ELECTRODES AS DESCRIBED IN NEC 250.52(A)(1)-(A)(7) THAT ARE PRESENT AT EACH BUILDING OR
2020 MINNESOTA BUILDING CODE STRUCTURE SERVED SHALL BE BONDED TOGETHER TO FORM THE GROUNDING ELECTRODE SYSTEM. WHERE NONE OF
Maryam Hadavi
2020 MINNESOTA RESIDENTIALCODE THESE GROUNDING ELECTRODES EXIST, ONE OR MORE OF THE GROUNDING ELECTRODES SPECIFIED IN NEC 5466 W Bavarian
2020 MINNESOTA FIRE CODE 250.52(A)(4)-(A)(8) SHALL BE INSTALLED PER NEC 250.50. ADDITIONAL GROUNDING ELECTRODES SHALL BE INSTALLED Pass Fridley MN
PER NEC 250.53. THE GROUNDING OR BONDING CONDUCTOR SHALL BE CONNECTED TO THE GROUNDING 554326122220990
ELECTRODE BY LISTED CLAMPS PER NEC 250.70.
B. ROOFTOP MOUNTED PHOTOVOLTAIC SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S
INSTALLATION INSTRUCTIONS. ROOF PENETRATIONS SHALL BE FLASHED AND SEALED IN ACCORDANCE WITH IRC UTILITY:
R909.3
C. ACCESS AND WORKING SPACE SHALL BE PROVIDED AND MAINTAINED ABOUT ALL ELECTRICAL EQUIPMENT TO PERMIT Xcel Energy -
READY AND SAFE OPERATION AND MAINTENANCE OF SUCH EQUIPMENT PER NEC 110.26. Minnesota
D. ALL PLAQUES AND SIGNS WILL BE INSTALLED AS REQUIRED BY NEC. DESIGNER:
E. CONDUIT WILL BE INSTALLED IN COMPLIANCE WITH NEC 358.
F. GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED PER NEC 250.64(B) AND SHALL BE CONTINUOUS PER Joseph Draut
NEC 250.64(C). DATE:
G. ROOF COVERINGS SHALL COMPLY WITH IBC 1506.2, 1507 & IRC R904.3. 8/9/2022
H. CIRCUIT BREAKERS, IF BACKFED, SHALL BE SUITABLE FOR SUCH OPERATION PER NEC 705.12(B)(4) AND WILL BE PROJECT#:
INSTALLED PER NEC 408.36(D). P-247104-22
I. INVERTERS UL LISTED 1741 PER IRC R324.3. Financier:
J. ROOFTOP MOUNTED PHOTOVOLTAIC PANEL SYSTEM SHALL BE TESTED, LISTED AND IDENTIFIED WITH A FIRE SDMCU
CLASSIFICATION IN ACCORDANCE WITH UL 1703.
K. NON-CURRENT-CARRYING METAL PARTS OF EQUIPMENT, RACEWAYS, AND OTHER ENCLOSURES, IF GROUNDED, SHALL
BE CONNECTED TO AN EQUIPMENT GROUNDING CONDUCTOR BY ONE OF THE METHODS SPECIFIED IN NEC JURISDICTION:
I hereby certify that this
plan.specification.or 250.134(A) OR (B). Fridley
report was prepared by me L. THE DISCONNECTING MEANS FOR UNGROUNDED CONDUCTORS SHALL CONSIST OF A MANUALLY OPERABLE SYSTEM SIZE:
or under my direct 7.4 KW-DC
supervision and that I am a SWITCHES OR CIRCUIT BREAKERS COMPLYING WITH NEC 690.15(D)(1).
duly Licensed I M. THE INSTALLATION OF EQUIPMENT AND ALL ASSOCIATED WIRING AND INTERCONNECTIONS SHALL BE PERFORMED 5 KW-AC
Engineer and r e SHEET TITLE:
the state of in ONLY BY QUALIFIED PERSONS PER NEC 690.4(C).
TITLE SHEET
N. IT IS THE DUTY OF THE PERSON REQUESTING ANY INSPECTIONS REQUIRED BY THE IRC TO PROVIDE ACCESS TO AND
Signature: VERSION:
License Number: 57699-6 MEANS FOR INSPECTION OF SUCH WORK PER IRC R109.3.
Digitally sealed by 0. SMOKE ALARMS & CARBON MONOXIDE ALARMS MUST BE INSTALLED PER IRC R314.2.2 AND R315.2.2. 3.3.6
Arlo HuUt/19)50U 3 P. SOLAR PV MODULES CANNOT BE INSTALLED OVER OR BLOCK ANY ATTIC VENTS, PLUMBING VENTS, FURNACE OR SHEET#:
Date: U PV01
AZIMUTH AND TILT TABLE
ROOF AZIMUTH TILTANGLE TILTANGLE MODULE SOLAR ROOF TYPE i 15'-311 '� 1 501dus
OF PANEL OF ROOF COUNT ACCESS
A 270 12 12 18 92% Asphalt Shingle
p g REGIONAL OFF ICE:
B 270 12 12 2 95% Asphalt Shingle 31 SOLCIUS, LLC
C O
TYP. 9124 GRAND AVE
D S SUITE 105
E MINNEAPOLIS,
F 3 MN 55420
G
(844) 357-2258
H
1 /o m CUSTOMER:
ZNSHINE ZXM6-NH120-370/M TOTAL:20 38 /0 O Cz
NEP BDM-300X2 1_�+11
V MaryannHadavi
1
3, FIRE SETBACKS (IFC 605.11.1) DESIGN WILL MEET NEC 2017 REQUIREMENTS TYP. c� 5466 W Bavarian
�� Pass Fridley MN
3"VENTILATION LOCATION ON THE RIDGE SHALL NOT BE REQUIRED TO BE FREE OF OBSTACLES.- - - - - - - - - 1 61-511
55432 6122220990
GENERAL NOTES: O Equipment Labels 1 m
1. ALLTESTING SHALL BE PERFORMED BY 1 ROOF ACCESS
QUALIFIED PERSONNEL,WITH PROPER
2 JUNCTION BOX 4 UTILITY:
PERSONAL PROTECTIVE EQUIPMENT. 3 1 MICROINVERTER PER 2 PV MODULES (�
2. THE AC DISCONNECT SHOULD BE
4 CONDUITRUN I 1� Xcel Energy-
LOCATEDTOGETHER IN AREADILY ,I�--
2
ACCESSIBLE LOCATION WITHIN 10' OF THE 5 MAIN SERVICE PANEL Minnesota
3. 24/7 UNESCORTED KEYLESS ACCESS 6 BILLING METER
SHALL BE PROVIDED FOR THE METERS 7 FUSED UTILITYAC DISCONNECT 7 $ ALL EQUIPMENT WILL BE
ANDAC DISCONNECT, UNLESS BILLING
8 COMBINER PANEL 5INSTALLED WITHIN 10'OF THE MSP DESIGNER:
METER IS ALREADY BEHIND CUSTOMER'S 6 Joseph Draut
FENCE, IN THATCASE, AN XCEL
EXCEPTION FORM WILL BE SUBMITTED. INTERCONNECTION SHALL DATE:
BE SECONDARY 8/9/2022
4. UTILITYAC DISCON N ECT SHOULD BE TOTAL ROOF AREA: 1580SQFT XCEL POWER SUPPLY UNDERGROUND PROJECT#:
LOCATED WITHIN 10'OF THE MAIN PROPOSED SOLAR AREA: 392 SQFT NO CLEARANCE
SERVICE METER. PROPOSED SOLAR WEIGHT: 1137.29 Ib
DUPLEX CONCERNS P-247104-22
5. XCEL POWER SUPPLY GROUND PROPOSED% COVERAGE: 25% N Financier:
330340350 0 70 20 0 S D MC U
320 40
31 0
30 0
2s 70
28 30
W27 AZIMUTH 0 E JURISDICTION:
I hereby certify that this 26 00
plan.specification.or 24 16 Fridley
report Was prepared by me 230 30
20
or under my direct 22210200,9 0160 0140 SYSTEM SIZE:
supervision and that I am a 0' 017 7.4 KW-DC
duly Licen La.
al s
Engineer nd af 5 KW-AC
the state f n SHEET TITLE:
CROSSING STREET (310') SITE PLAN
Signature:
License Number: 57699-6
Digitally sealed by
Arlo Hu� 3.3.6
Date: �Z9in S Bavarian Pass SHEET#:
PV02
EQUIPMENT SCHEDULE Q CONDUIT AND CONDUCTOR SCHEDULE(PER NEC 690.8(B),TABLE 310.15(B)(2)(a),TABLE 250.122)
TAG DESCRIPTION MANUFACTURER PART NUMBER NOTES TAG CONDUCTORTYPE MIN.CONDUCTOR SIZE #OFCONDUCTORS CONDUITTYPE MIN.CONDUITSIZE '
1 SOLAR PANEL ZNSHINE ZXM6-NH120-370/M QUANTITY(20) OPTIMIZER CABLE #10 2
2 COMBINER PANEL SERVICE RATED 125A 1 IN FREE AIR N/A
3 MICRO INVERTER NEP NEPBDM-30OX2 QUANTITY(10)
BARE COPPER(EGC) #6 1
4 JUNCTION BOX PVC JUNCTION BOX(OR EQ.) 513371OU CANTEX THWN-2 #10 4 MC THROUGH ATTIC WHERE POSSIBLE,
2 3/4" REGIONAL OFFICE:
5 RACKING ECOFASTEN CLICKFIT ECOFASTEN CLICKFIT THWN-2/EGC #10 1 OTHERWISE EMT RUN ON ROOF
6 FUSED UTI UTYAC DISCONN ECT EATONOREQUAL DG222NRB,24OV,60A,2P,3R FUSE S17ES:30A,LOCKABLE 3 THWN-2 #10 3 EMT 3/4" SOLCIUS, LLC
7 THWN-2/EGC #10 1 9124 GRAND AVE
9 4 THWN-2 #6 3 EMT 3/4" S SUITE 105
10
MINNEAPOLIS,
11
12 MAIN SERVICE PANEL I MN 55420
INVERTER SPECIFICATIONS PV MODULE SPECIFICATIONS (844) 357-2258
MANUFACTURER NEP MAKE ZNShine
MODEL BDM-300X2 MODEL ZXM6-NH120-370/M CUSTOMER:
MAX DC INPUT VOLTAGE [VI 60 MAX POWER-POINT CURRENT(I_) [A] 10.82
MAX OUTPUT POWER [W] 580 MAX POWER-POINT VOLTAGE(V_) (VI 34.2
NOMINAL AC OUTPUT VOLTAGE [VI 240 OPEN CI RCUITVOLTAGE(Voj (VI 41
NOMINALACOUTPUT CURRENT [A] 2.09 SHORT CIRCUIT CURRENT(I'd [A] 11.42
REQUIRED OVERCURRENT PROTECTION [AJ 40 MAX POWER P [W] 370
Maryam Hadavi
EXISTING MAIN SERVICE PANEL INFORMATION 5466 W Bavarian
VOLTAGE: 1201240 [V] Pass Fridley MN
PHASES: 1 0
BOX/BUS RATING: 100 [A] 55432 6122220990
MAIN BREAKER: 100 [A]
PV AMPERAGE: 30 [A]
FEED TYPE: End Fed
CALCS: (100A B US)*(1)=100A MAX UTILITY:
10 MODULES IN A CIRCUIT NEC 705.12(A) BUS RATING SUPPLY SIDE
MAIN BREAKER TAP
(100A)=(100<=100) XceI Energy-
ESTIMATED ANNUAL PRODUCTION:7273 KWH Minnesota
NOTE: INTERCONNECTION
J-Box WILL BE MADE USING THE DESIGNER:
— + — + — + K4977-INT DUAL LUG KIT. 12
— — — Joseph Draut
PV SHALL BE INSTALLED ON SUPPLY
/V /V /V SIDE OF SERVICE DISCONNECTING DATE:
MEANS IN ACCORDANCE WITH NEC
I -- 705.12(A). 8/9/2022
PROJECT M
10 MODULES IN A CIRCUIT
P-247104-22
Financier:
BILLING
• • • TO NEP BDG-256 MONITORING METER TO SDMCU
NEW SUB PANEL
J-BOX (2)20A-2P CIRCUIT BARE COPPER#6, OTHER
+ BREAKERS LOADS
(1)15A-2P MONITORING 8'X5/8" GROUNDING
BREAKER ROD JURISDICTION
• • • / 10oa-2P Fridley
SYSTEM SIZE:
7.4 KW-DC
5 KW-AC
SERVICE SHEET TITLE:
CONDUCTORS ELECTRICAL LINE
1 2 3 4 BARE COPPER#6 EXTENDING TO = DIAGRAM
3 1 5 4 2 6 - UTILITY VERSION:
3.3.6
APPROX SHEET
SOLAR EQUIPMENTON THE ROOF SOLAR EQUIPMENT S FROM THE MSP
75 ft PV03
Main Service Panel AC Disconnect Combiner Box
( If Used) REGIONAL OFFICE:
O SOLCIUS, LLC
9124GRANDAVE
S SUITE 105
FOR ILLUSTRATION ONLY MINNEAPOLIS,
(NOT ACTUAL PANEL)
MN 55420
(844) 357-2258
FOR ILLUSTRATION ONLY FOR ILLUSTRATION ONLY WARNING CUSTOMER:
(NOT ACTUAL MSP) (NOT ACTUAL DISCONNECT)
PHOTOVOLTAIC SYSTEM
SOLAR PV SYSTEM EQUIPPED COMBINER PANEL
WITH RAPID SHUTDOWN PY11TIVILTAIC AC IISO# DO NOT ADD LOADS Maryam Hadavi
TURN RAPID SHUTDOWN 5466 W Bavarian
SW_FFITCH TO THEON , RATED
. OUTPUT ,
SHUTD"WN RSPV SYSTEM
... ARRAY RD NOMINAL OPERATING„ , VOLTAGE: 40 Pass Fridley MN
55432 6122220990
DISCONNECTUTILITY AC
,WARNING
ELECTRICAL SHOCK HAZARD UTILITY:
,WARNING DUAL POWER SOURCE TERMINALS ON BOTH LINE AND
SECOND SOURCE IS PHOTOVOLTAIC SYSTEM LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
jL Xce I Energy -
II Minnesota
DESIGNER:
WARNING
Joseph Draut
rov
WER SOURCE OUTPUT
NNECTION. DO NOT DATE:
RELOCATE THIS
ERCURRENT DEVICE. 8�9�2022
PROJ ECT#:
IL P-247104-22
Financier:
SDMCU
WARNING: PHOTOVOLTAIC
POWER SOURCE
'LOCATION: EVERY 10'ALONG ANY CONDUITS OR MC CABLE THAT CONTAIN DC CIRCUITS, JURISDICTION:
AT EVERY ENCLOSURE,AND AT EACH SIDE OF WHERE THE CONDUIT OR CABLE PASSES
THROUGH A WALL, FLOOR, OR ANY OTHER PARTITION. Fridley
SYSTEM SIZE:
NOTES: DC CONDUIT MUST BE A REFLECTIVE STICKER
7.4 KW-DC
NOTES: 5 KW-AC
SHEET TITLE:
EQUIPMENT
LABELS SHALL BE WEATHERPROOF, DURABLE,AND PERMANTLY MOUNTED LABELS
VERSION:
FOLLOWINGTHE 2017 NATIONIONAL ELECTRIC CODE (NEC) (690) 3.3.6
DESIGN WILL MEET NEC 2017 REQUIREMENTS SHEET#:
PV04
LABEL ROOF TYPE MOUNTING TYPE AREA OF ARRAY GROSS WEIGHT DEAD LOAD RATING EXISTING STRUCTURAL FRAMING MAX RAIL SPAN RAILSPAN OFFSET
ROOF A ASPHALT SHINGLE GF-1 353 SQ. FT. 774 IBS. 2.19 LBS/SQ.FT. 2X4 @24" O.C. 4' 2'
ROOF B ASPHALTSHINGLE GF-1 39.2SQ. FT. 861BS. 2.19 LBS/SQ.FT. 2X4 @24" O.C. 4' 2'
REGIONAL OFFICE:
SOLCIUS, LLC
9124 GRAND AVE
S SUITE 105
MINNEAPOLIS,
MN 55420
(844) 357-2258
■= STANDOFF ATTACHMENT SPACING CUSTOMER:
3'-2"
3'-2"
2' TYP. Maryam Hadavi
2' TYP. 5466 W Bavarian
Pass Fridley MN
4' TYP. 55432 6122220990
4' TYP.
UTILITY:
41 XceI Energy-
Minnesota
DESIGNER:
Q Joseph Draut
IL
O DATE:
Q 8/9/2022
PROJECT#:
2' 2'
P-247104-22
Financier:
2'TYP. 2'TYP. SDMCU
4'TYP. m 4'TYP.
I hereby certify that this LL JURISDICTION:
plan,specification,or 0 Fridley
report was prepared by me O
or under my direct 121� SYSTEM SIZE:
supervision and that I am a
7.4 KW-DC
duly Liceofn
La.
al
Engineerf 5 KW-AC
the state
SHEET TITLE:
ATTACHMENT
Signature: SPACING
License Number: 57699-6
VERSION:
Digitally sealed by
Aria HuliJ1�/���I 3.3.6
Date: U SHEET#:
THE MAX CANTILEVER IF ANY WILL NOT EXCEED 1 '6" PV05
ATTACHMENT DETAIL
solcius
REGIONALOFFICE:
SOLCIUS, LLC
214
ROOF TYPE SHOWN IN PROJECT F —9 3'VIP, 9124 GRAND AVE
SPECS TABLE BELOW FLASHING S SUITE 105
"= MINNEAPOLIS,
MN 55420
(844) 357-2258
CUSTOMER:
Maryam Hadavi
5466 W Bavarian
Pass Fridley MN
SEE RAFTER SIZE SHOWN IN PROJECT SPECS TABLE BELOW 5 ass Fridley
ELEVATION VIEW UTILITY:
Xcel Energy -
Minnesota
SOLAR 190DULE
DESIGNER:
Joseph Draut
ROOF TYPE SHOWN IN PROJECT 6" MAX FROM TOP OF ROOF DATE:
SPECS TABLE BELOW I _f01 I 3 MIN TO TOP OF SOLAR PANEL 11)�1 I FLASHING 8/9/2022
PROJECT#:
P-247104-22
Financier:
f I SEE RAFTER SIZE SHOWN IN / SDMCU
PROJECT SPECS TABLE BELOW
I hereby certify that this f l JURISDICTION:
plan.specification.or
report was prepared by me /L Fridley
or under my direct I SYSTEM SIZE:
supervision and that l am a b ATTACHNIENT SPACING-- 7.4 KW-DC
duly Licens ional
Engineer a rs o€ 5 KW-AC
the state a. PROJECTSPECS
SHEET TITLE:
Signature: RAFTER SIZE: 2x4" RACK& RAIL
DIAGRAM
License Number: 57699-6 RAFTER SPACING: 24" O.C. VERSION:
Digitally sealed by ROOF TYPE: Asphalt Shingle
Date:
HUR19)50�3 ATTACHMENT SPACING: Max 4' 3.3.6
Da
�s RAILS/ RACKING: ECOFASTEN CLICKFIT SHEET#:
MOUNTING: GF-1 PV06
ZXM6-NH120ZNSHINE O ZXM6-NH120 Serie, Znshinesolar9BB HALF-CELL ZNSHINESOLAR
monocrystalline PV Module
ELECTRICAL PROPERTIES I STC*
r r r r .r r r r
Mono Nominal Power Watt Pmax(M 350 355 360 365 370
Power• 1 0-+3 0-+3 0-+3 0-+3
Maximum Power Voltage Vmp(V) 33.4 33.6 33.8 34.0 34.2
350W 1355W 1 360W 1365W 1370W Maximum Power Current I mp(A)111111 111111 11111111111111111111111111111111 10.48 10.57 10.66 10.74 10.82
Made with selected materials and components to grant quality, dura- IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII Open Circuit Voltage VocM 40.2 40.4 40.6 40.8 41.0
tion, efficiency and through outputs, the ZXM6-NH120 monocrystal- IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII
Short Circuit Current Isc(A)line modules by ZNSHINE SOLAR( power output 350 up to 370Wp, IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII 11.04 11.14 11.24 11.33 11.42
represent a highly flexible solution for diverse Installation types,from IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIModule Efficiency(0/6) 18.80 19.07 19.34 19.61 19.88
industrial rooftop plants to small home PV systems or large ground *STC(Standard Test Condition):Irradiance 1000w/m2,Module Temperature 25°C,AM 1.5
surfaces.This allows you to produce clean energy while reducing your IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII The data above is for reference only and the actual data is in accordance with the pratical testing
energy bill. IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII ELECTRICAL PROPETIES I NMOT*
IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII ZNSHINE SOLAR' S ZXM6-NH120 Monocrystalline solar modules are 256.1 259.8 263.5 267.1 270.EIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII
tested and approved by international acknowledged laboratories, so IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII 30.9 3� 31.3 31.4 31.6
that we can offer our customers a reliable and price-quality optimized IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII
product. The linear warranty on product outputs further ensures 8.28 8.36 8.43 8.50 8.57
increased security and return on investments over time. IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII •. 37.2 37.4 in. 37.6 37.8 38.0
12 years product warranty/25 years output warranty IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII 8.92 9.00 9.08 9.1s 9.22
IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII IIIIIIIIII *NMOT(Nominal module operating temperature):Irradiance 800w/m',Ambient Temperature 20°C,AM 1.5,Wind Speed 1m/s
0.55%Annual Degradation over 25 years IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII IIIIIIIIII The data above is for reference only and the actual data is in accordance with the pratical testing
Znshine'sStandard IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII TEMPERATURE RATINGS MECHANICAL DATA
1
Industry Standard IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII • 44°C±2°C Mono 166x83mm
97.5% IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII
fl- -
� IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIITemperature coefficient orl'Pmax -0.36%/°C 120 (6x20)
3 IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIITemperature coefficient of Voc -0.2996/°C 1776x1048x35 mm
DO 90% IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIITemperature coefficient of Isc 0.05'Yo/*C 19.5 kg
*Do not connect Fuse in Combiner Box with two or more strings in parallel connection
lo 84.3% High transparency,low iron,tempered
80%
ro WORKING CONDITIONS Glass 3.2 mm(AR-coating)
1 5 12 15 25 Years Maximum system voltage 1000/1500 V DC IP 68, 3 diodes
•.- -40°C-+85°C 4 mm2,350 mm
9 Busbar Solar Cell High Efficiency Maximum series fuse IIIIIIIII
9BB No power loss thanks to improved temperature Graphene coating can increase about 2W of the module 20 A MC4-compatible
5400 Pa/2400 Pa
co-efficient caused by 9 busbar solar cell efficiency by rising around 0.5%of the light transmission Maximum load(snow/wind)
PACKAGING INFORMATION
DIMENSION OF THE PV MODULE (mm) 40' HQ
Anti PID Better Weak Illumination Response BsrcodeI 30
P11 D Limited power degradation of ZXM6-NH 120 module Lower temperature coefficient and wide spectral fi 8%3 m 840
caused by PID effect is guaranteed under strict testing y response,higher power output,even under low-light ^e2 1Z''
condition for mass production settings
I-V CURVES OF THE PV MODULE
„x.9 ,° 1 410
Certified to withstand the most 370
�Grahpene Coating m ' °°°w'^°
challenging environmental conditions • 330
Graphene coating modules can increase power generation 1111111 "° B BB1 =aa°w1m°
A 5400 Pa snow load a
2400 Pa wind load and self-cleaning,also can save maintainance cost � �A "° R
v , 210 ;, =°aa wim=
nAInA 0 9 170
oa V a
130 =400./
T
O° E PV CYCL EdQui�eV, Oe
so =�oowimA
nvnerto rtekC U vM UAL, nQ » XX �
0 0
10 20 30 40 s0
ZNShine PV-Tech Co., LTD,founded in 1988, is a world-leading high-performance PV module manufacturer, PV power station developer, EPC and power station Voltage M
operator.With its state-of-the-art production lines,the company boasts module output of 5GW.Bloomberg has listed ZNShine as a global Tier 1 PV manufacturer and
Top 4 reliable PV supplier. Add:1#,Zhixi Industrial Zone, JintanJiangsu 213251, P.R.China Remark:please read safety and installation instructions before using the product I Subject
www.znshinesolar.com Tel: +86 519 6822 0233 E-mail: info@znshinesolar.com to change without prior notice®ZNSHINE SOLAR 20201 Version:ZXM6-NH120-2004.E
north_ _ Recommended Max PV Power(W ) 450x2
Max DC Open Circuit Voltage(Vdc) 60
Max DC Input Current(Ado) 14 x 2
• INPUT(DC) MPPT Tracking Accuracy >99.5%
�. 0 MPPT Tracking Range(Vdc) 22-55
` � � }: �•• � , � Ise PV(absolute maximum)(Ado) 18 x2
`� Maximum Inverter Backfeed Current to the Array(Adc) 0
NO ELECTRIC ` 'ti P
}}� N R A T N E A N ELECTRIC Peak AC Output Power(W p) 580
1 f•]'•r0••t Rated AC Output Power(W p) 500
BDM-300X2 I�ii�i nonraEaA ELECiAiC Y Nominal Power GridVoltage(vac) 240 208 230
BDM-30OX2 Allowable Power 0 id Voltage(Vac) 211-264* 183-229* configurable*
Allowable Power Grid Frequency(Hz) 59.3-60.5* I configurable*
MICROINVERTER MICROINVERTER THD r3%(at rated power)
OUTPUT(AC) Power Factor(cos phi,fixed) >0.99(at rated power)
Features Rated Output Current(Aac) 2.09 2.40 2.17
10.91 1.97 current(inrush)(Peak and Duration 24A,15us
0 •Low Cost$/watt micro inverter Nominal Frequency(Hz) 60 1 50
W •High peak output power up to 580Wac,recommended Maximum Output Fault Current(Aac) 2 4Arms for 3 cycles
for dual max 385W solar panel lIII�� Maximum Output Overcurrent Protection(Aac) 10
�—' •High efficiency with 95.5%CEC ! `��� Maximum Number of Units Per Branch(20A)cons 7 6 6
g y n o I`I` (All NEC adjustment factors have been considered)
•Globally certified for UL1741,SAA,TUV,VDE-AR-N 4105,VDE I' noel+En.:.,:.:�: SYSTEM EFFICIENCY Wei hted Avera ed Efficiency(CEC) 95.50%
fill 0126,083/2,CEL 021,IEC61727,EN50438,ABNT NBR 6149/16150 Ni htTimeTareLoss Wp 0.11
•Integrated grounding for installation 520' 013W Over/Under Voltage Protection Yes
O
9 9 9 Y ���ri�i�ei naa Over/Under Frequency Protection Yes
�_ •NEMA-6/IP-66/IP-67 enclosure rating AntFlslanding Protection Yes
-� _ o o
•Integrated monitoring and power line communication Over Current Protection Yes
Reverse DC Polo rity Protection Yes
with RDG256 gateway Overload Protection Yes
•Can connect with BDM-300 an@I BDM-250 .-- Protection Degree NEMA-6/IP-66/IP-67
Ambient Temperature -400F to+1490F(-40°C to+65°C)
(��N�,► /// ///��� �i Operating Temperature -407to+1650F(-40°Cto+g5°C)
Us ( ♦ SAA Display LED LIGHT
i+ m ` ` t52167 �U
Comunications Power Line
PROTECTION Dimension(w-H-D) 10.91"x5.20"xl.97'(277xl32x50mm)
•+ t FUNCTIONS Weight 6A lbs.(2.9 kg)
'Grid parameters are configurable through a BDG-256 or Environment Category Indoor and outdoor
Important product information BDG-256P3 gateway Wet Location Suitable
•All NEC required adjustment factors have boon Pollution Degree PD 3
•NEP is committed to developing Clean,Affordable,Reliable and considered for AC outputs.AC current outputs will not Overvoltage Category II(PV),III(AC MAINS)
Efficient(CARE)products for our customers worldwide. exceed stated values for Rated Output AC Current UL1741
Product Safety Compliance CSA C222 IEC/EN 62109-1
•NEP rnlCfOinV9rt9r5 have an isolation transformer and basic COMPLIANCE IEC/EN 62109-2
*NEC 2020 Section 690.11 DC Are-Fault Circuit Protection No.107.1
isolation between the DC input and the AC output network. 'NEC 2020 Section 690.12 Rapid shutdown of PV systems art
P Y VDE-AR-N 4105'
Buildings Grid Code Compliance*(Refer to the label for the VDE v012s-1-1/A1
'NEC 2020 Section 705.12 Point of Connection(AC Are-Fault detailed grid code compliance) IEEE 1547 083/2,CB 021
Protection) As 47772 a As
4777.3,EN50438
ABNT NNR 18140/1815
RtVIf10N DA1l:p/)/=2 YERf10N:Y2.7
PRODUCT .� E c o F asten.
For InstaLLers. By Instal[Lers.
EcoFasten,
CF , RAIL l . MLL 171 .5" INSTALLATION ' •
PART NUMBER DESCRIPTION RATINGS
2012025 CF STD RAIL AL MLL 171.5"
Fire Rating* Class A System Fire Rating
Max System Voltage 1500 VDC
1 Max Fuse Rating 40A
Certification Conforms to UL STD 2703
Warranty 25 Year Material and Workmanship
UL 2703 Markings Product listing label is located on the rail end-caps
Roof Pitch 2:12-12:12
UL 2703 Allowable Design Load Rating 10 psf downward,5 psf upward,and 5 psf lateral
Max Module Size 25.6 sgft
Module Orientation Portrait or Landscape
ITEM NO. DESCRIPTION 1 CF STD RAIL MILL AL RAIL EXTRUSION PROFILE, [4356.1 MM] LONG Multiple use Rated Components(Position Independent) Mid Clamp,Frame MLPE Mount and MLPE Mount
\*Class A System fire rating with Type 1 &2 PV modules.Any module-to-roof gap is permitted,with no skirt required.This rating is
1) CF STD RAIL MILL AL RAIL EXTRUSION PROFILE, [4356.1 MM] LONG applicable with any roof attachment.
UL 2703 MARKING EXAMPLE.
-0 v Ac -
171 .5 CLICKFIT
SYSTEM
MFG . .. ..
Conforms to UL STD 2703
0000
TORQUE SPECIFICATIONS
Component Torque(in-lb) Notes
Lag Screw N/A Fully Seat.Use visual indicator of the black EPDM ring around the
1 .57- bonded washer for torquing.
Mid-Clamp 144
End-Clamp 96
Rail Clicker Leveling Bolt 142 Pre-torqued upon delivery.Applies to Tile Hook and L-Foot/Clicker
1 .57 Hook Height Bolt N/A Lightly clamp hook to flush with top of next tile row
Ground Lug N/A Refer to specific ground lug manufacturer's installation manual
MLPE Clip 144
MLPE Mount 144
Material Aluminum
Finish Mill
REV.- CS1 PAGE
1 .
RtVK10N YA7�q/)/72 Y[IISION:v2.7 \ RtVIf10N DA1l:p/)/=2 YERf10N:Y2.7
'�'INSTALLATION GUIDE V '�' EcoFasten.
BONDING AND GROUNDING ' MODULES
VSUN modules with 30,35 and 40 mm frames
BONDING PATHS VSUN VSUNxxx-YYz-aa
Bonding paths are carried throughout the array in a variety of ways. They are carried module- Where'W'can be 60, 72, 108, 120,or 144;"z"can be M, P, MH, PH, or BMH;
to-module and module-to-rail through mid clamps, carried at rail-to-rail connections through and"aa"can be blank, BB or BW
Waaree modules with 40mm frames
the bondingjumpers, and carried row-to-row using bondingjumpers either module-to-module Waaree Waaree x
on the module frame or rail-to-rail on the ends of the rails. I where"yy'can be blank or M
Winaico modules with 35 and 40 mm frames
Winaico „ ,
Wsy-xx a
.„
MID CLAMP Where can be either P or T, Z„ „can be either M, P, or MX; and a„can be
2 mid clamps bonding blank or 6
pairs of modules Yingli modules with 35 and 40 mm frames
GROUNDING LUG Yingli YLxxxZ-yy
1 ground lug per Where"Z"can be D or P;"yy"can be 29b,30b,34d,35b,36b or 40d
continuous array
ZN Shine modules with 35mm frames
ZN Shine ZXMY-AAA-xxx/M UJ
Where"Y"can be 6 or 7,"AAA"can be 72, NH120, NH144 or NHDB144
C3 moi
IIIIIIIIIIIIJ C3
\ O
\ O
�
RAIL SPLICE
1 splice bonding
MODULE JUMPER adjacent pair of rails
1 module jumper
bonding module to
module and row to row PAGE
. . � � j.
GF-1 FLASHING GLV BLK 8X1211
PART NUMBER DESCRIPTION
3012010 GF-1 FLASHING GLV BLK 8X12"
1
ITEM NO. DESCRIPTION
1 GF1-GAL-BLK-812
1) GF1-GAL-BLK-812
8.0
12.0
00.3 THRU
.WYY
0.02
0.31
Material Corrosion Resistant Steel
Finish Black
REV.- CS 1