STRUCTURAL CALCULATIONS
Cameron Residence Floor Support
5924 Oakwood Manor NE, Fridley, MN 55432
• • 2�
LICENSED ••
PROFESSIONAL ;
• ENGINEER —
%N• 58974 Q�
''OF 1M 110
`��
PROFESSIONAL ENGINEER
I hereby certify that this plan, specification, or
report was prepared by me or under my direct
supervision and that I am a duly Licensed
Professional Engineer under the lows of the
State of Minnesota
Print Name:
Signature:-
Date08-30-bq2 License # 58974
LIMITATIONS
ENGINEER WAS RETAINED IN A LIMITED CAPACITY FOR THIS PROJECT.DESIGN IS BASED
UPON INFORMATION PROVIDED BY THE CLIENT WHO IS SOLELY RESPONSIBLE FOR
ACCURACY OF SAME.NO RESPONSIBILITY AND/OR LIABILITY IS ASSUMED BY,OR IS TO BE
ASSIGNED TO THE ENGINEER FOR ITEMS BEYOND THAT SHOWN ON THESE SHEETS.
Project No. IBA22-378
August 30,2022
[� 5FA Design Group, LLC
®� STRUCTURAL I GEOTECHNICAL I SPECIAL INSPECTIONS PROJECT NO. SHEET NO.
IIBA22-378
PROJECT DATE
Cameron Residence Floor Support 8/30/2022
SUBJECT BY
IntelliJack(Steel Beam)/(wood Beam)& Intellibrace Design Requirements �BE
Structural Narrative
The structural calculations and drawings enclosed support the use of IntelliJacks for mitigation of observed structural settlements,
and support of the vertical loads tributary to it, at a residential property located in Fridley, MN as referenced on the
coversheet.IntelliJacks consist of a 3.5" square steel tube attached to a plate by a 1.25" diameter adjustable threaded rod. This
plate is attached to the bottom side of a supporting beam with (4) bolts with nuts.The steel pipe sits in a pre-fabricated base plate
that bears on a poured in place concrete footing.
The structural calculations and drawings enclosed are in reference to the design of the basement wall stabilization of the
residence located in Fridley, MN as referenced on the coversheet. Intellibrace systems are used to support and stabilize
foundation walls. Heavy-duty zinc plated steel beams are custom-fit to the basement wall with heavy-duty steel brackets that are
anchored to the basement concrete slab floor and floor joists. The steel beams will stabilize the wall in its current position, without
any further adjustment. The Intellibrace design gives the ability to continue to tighten the system during the dry season for possible
wall improvement.
General
Building Department City of Fridley
Building Code Conformance (Meets Or Exceeds Requirements)
2018 International Building Code (IBC)
2018 International Residential Code(IRC)
2020 Minnesota Building Code
2020 Minnesota Residential Code
Dead Loads
Floor Dead Load 15.0 psf
Interior Wall Dead Load 9.0 psf
Live Loads
Floor Live Load (Residential) 40.0 psf
Soil Parameters
Reference Standards Conform to CBC Chapter 18
"Soils & Foundations".
Allowable Foundation Pressure (Assumed) 1500 psf
LDeflections
Total Load Deflection Limit L/240
Live Load Deflection Limit L/360
Project Title:
Engineer:
Project I D:
Project Descr:
Steel Beam Project File: IBA22-378 Cameron Residence.ec6
LIC#:KW-06015057,Build:20.21.9.26 SFA ENGINEERING LLC (c)ENERCALC INC 1983-2021
DESCRIPTION: 7 ft Beam
CODE REFERENCES
Calculations per AISC 360-16, IBC 2018, CBC 2019, ASCE 7-16
Load Combination Set: IBC 2018
Material Properties
Analysis Method Allowable Strength Design Fy: Steel Yield : 50.0 ksi
Beam Bracing : Completely Unbraced E: Modulus: 29,000.0 ksi
Bending Axis: Major Axis Bending
D(0.1320)L(0.220)
S4x7.7 S4x7.7 Z S4x7.7
Span =2.0 ft Span =3.0 ft r�T Span =2.0 ft
I
J
Applied Loads Service loads entered. Load Factors will be applied for calculations.
Beam self weight NOT internally calculated and added
Loads on all spans...
Uniform Load on ALL spans : D= 0.0240, L=0.040 ksf, Tributary Width =5.50 ft
DESIGN SUMMARY •
Maximum Bending Stress Ratio = 0.081 : 1 Maximum Shear Stress Ratio = 0.046 : 1
Section used for this span S4x7.7 Section used for this span S4x7.7
Ma :Applied 0.704 k-ft Va :Applied 0.7040 k
Mn/Omega :Allowable 8.733 k-ft Vn/Omega :Allowable 15.440 k
Load Combination +D+L Load Combination +D+L
Location of maximum on span 2.000ft Location of maximum on span 2.000 ft
Span#where maximum occurs Span#1 Span#where maximum occurs Span#1
Maximum Deflection
Max Downward Transient Deflection 0.012 in Ratio= 3,846 —360 Span:3: L Only
Max Upward Transient Deflection -0.003 in Ratio= 13,685 —360 Span:3: L Only
Max Downward Total Deflection 0.020 in Ratio= 2404 —240. Span:3:+D+L
Max Upward Total Deflection -0.004 in Ratio= 8553 —240. Span:3:+D+L
Vertical Reactions Support notation : Far left is#' Values in KIPS
Load Combination Support 1 Support 2 Support 3 Support 4
Overall MAXimum 1.232 1.232
Overall MINimum -0.277 -0.277
D Only 0.462 0.462
+D+L 1.232 1.232
+D+0.750L 1.040 1.040
+0.60D 0.277 0.277
L Only 0.770 0.770
Project Title:
Engineer:
Project I D:
Project Descr:
General Beam Analysis Project File: IBA22-378 Cameron Residence.ec6
LIC#:KW-06015057,Build:20.21.9.26 SFA ENGINEERING LLC (c)ENERCALC INC 1983-2021
DESCRIPTION: (E) Wood Beam Top
General Beam Properties
Elastic Modulus 29,000.0 ksi
Span#1 Span Length = 2.0 ft Area= 10.0 inA2 Moment of Inertia = 100.0 inA4
Span#2 Span Length = 4.0 ft Area= 10.0 inA2 Moment of Inertia = 100.0 inA4
Span#3 Span Length = 4.0 ft Area= 10.0 inA2 Moment of Inertia = 100.0 inA4
Span#4 Span Length = 4.0 ft Area= 10.0 inA2 Moment of Inertia = 100.0 inA4
Span#5 Span Length = 4.0 ft Area= 10.0 inA2 Moment of Inertia = 100.0 in^4
Span#6 Span Length = 4.0 ft Area= 10.0 inA2 Moment of Inertia = 100.0 inA4
Span#7 Span Length = 4.0 ft Area= 10.0 inA2 Moment of Inertia = 100.0 inA4
Span#8 Span Length = 2.0 ft Area= 10.0 inA2 Moment of Inertia = 100.0 in^4
D(0.3360)L(0.560)
X X X X X
Span=2.0 ft Span=4.0 ft Span=4.0 ft Span=4.0 ft Span=4.0 ft Span=4.0 ft Span=4.0 ft San=2.0 ft
Applied Loads Service loads entered. Load Factors will be applied for calculations.
Loads on all spans...
Uniform Load on ALL spans : D= 0.0240, L=0.040 k/ft, Tributary Width = 14.0 ft
DESIGN SUMMARY
Maximum Bending= 1.268 k-ft Maximum Shear= 1.879 k
Load Combination +D+L Load Combination +D+L
Span#where maximum occurs Span#2 Span#where maximum occurs Span#6
Location of maximum on span 4.000 ft Location of maximum on span 4.000 ft
Maximum Deflection
Max Downward Transient Deflection 0.000 in 0
Max Upward Transient Deflection 0.000 in 0
Max Downward Total Deflection 0.000 in 99082
Max Upward Total Deflection -0.000 in 536063
Vertical Reactions Support notation : Far left is#' Values in KIPS
Load Combination Support 1 Support 2 Support 3 Support 4 Support 5 Support 6 Support 7 Support 8 Support 9
Overall MAXimum 0.435 3.062 3.694 3.552 3.600 3.552 3.694 3.062 0.435
Overall MINimum
D Only 0.163 1.148 1.385 1.332 1.350 1.332 1.385 1.148 0.163
+D+L 0.435 3.062 3.694 3.552 3.600 3.552 3.694 3.062 0.435
+D+0.750L 0.367 2.583 3.117 2.997 3.037 2.997 3.117 2.583 0.367
+0.60D 0.098 0.689 0.831 0.799 0.810 0.799 0.831 0.689 0.098
L Only 0.272 1.914 2.309 2.220 2.250 2.220 2.309 1.914 0.272
Project Title:
Engineer:
Project I D:
Project Descr:
General Beam Analysis Project File: IBA22-378 Cameron Residence.ec6
LIC#:KVV-06015057,Build:20.21.9.26 SFA ENGINEERING LLC (c)ENERCALC INC 1983-2021
DESCRIPTION: (E) Wood Beam Bot
General Beam Properties
Elastic Modulus 29,000.0 ksi
Span#1 Span Length = 2.0 ft Area= 10.0 inA2 Moment of Inertia = 100.0 inA4
Span#2 Span Length = 4.660 ft Area= 10.0 inA2 Moment of Inertia = 100.0 inA4
Span#3 Span Length = 4.660 ft Area= 10.0 inA2 Moment of Inertia = 100.0 inA4
Span#4 Span Length = 4.660 ft Area= 10.0 inA2 Moment of Inertia = 100.0 inA4
Span#5 Span Length = 2.0 ft Area= 10.0 inA2 Moment of Inertia = 100.0 in^4
ID(02040)L(O.340)
b �
X X X X
Span=2.0 ft Span=4.660 ft Span=4.660 ft Span=4.660 ft Span=2.0 ft
Applied Loads Service loads entered. Load Factors will be applied for calculations.
Loads on all spans...
Uniform Load on ALL spans : D= 0.0240, L=0.040 k/ft, Tributary Width =8.50 ft
DESIGN SUMMARY
Maximum Bending= 1.030 k-ft Maximum Shear= 1.327 k
Load Combination +D+L Load Combination +D+L
Span#where maximum occurs Span#4 Span#where maximum occurs Span#4
Location of maximum on span 0.000 ft Location of maximum on span 0.000 ft
Maximum Deflection
Max Downward Transient Deflection 0.000 in 0
Max Upward Transient Deflection 0.000 in 0
Max Downward Total Deflection 0.001 in 100237
Max Upward Total Deflection -0.000 in 426634
Vertical Reactions Support notation : Far left is#' Values in KIPS
Load Combination Support 1 Support 2 Support 3 Support 4 Support 5 Support 6
Overall MAXimum 0.167 2.129 2.594 2.594 2.129 0.167
Overall MINimum
D Only 0.063 0.799 0.973 0.973 0.799 0.063
+D+L 0.167 2.129 2.594 2.594 2.129 0.167
+D+0.750L 0.141 1.797 2.189 2.189 1.797 0.141
+0.60D 0.038 0.479 0.584 0.584 0.479 0.038
L Only 0.104 1.331 1.621 1.621 1.331 0.104
[� 5FA Design Groups LLE PROJECT NO. SHEET NO.
®� STRUCTURAL I GEOTECHNICAL I SPECIAL INSPECTIONS IBA22-378
PROJECT DATE
Cameron Residence Floor Support 8/30/2022
SUBJECT BY
Project Layout BE
Pier Layout(See S2.1 for Enlarged Plan)
O O
29'-4"
o
i
1 r----------------------------
I
I Iw I I
16 I to I I I
I o p I I
I I I BIZ I I
3-0" 12'-0"
S4x7.7 OB
2'-0' I r^ — (6) EO ISPACESIJ
J L-J L-J L-J L-J L-J L-J I
I r(E) DROPPED BEAM TYPI I
I r—� r—� r—� J
+O+-
31 I I I
I 6'-p" (3) EQ SPACES 8'_0^ I I
I I 2'-0"SQx6"DP 3/4" MINUI I
I I COMPACTED CRUSHED I I
2 1 I STONE FTC W/ IJ-IC
(E) CONIC SLAB I ENDURACRETE FTG PER
I I ON GRADE I GENERAL NOTES TYP I I I
I I I I I
I I I I
O - I L -------------I-------------
2 L-----------------------------J
O
(V
(E) FOUNDATION/(N) INTELLIJACK/INTELIBRACE LAYOUT PLAN
z
SCALE NTS
[� SFA Design Group, LLC PROJECT NO. SHEET NO.
®� STRUCTURAL I GEOTECHNICAL I SPECIAL INSPECTIONS IBA22-378
PROJECT DATE
Cameron Residence Floor Support 8/30/2022
SUBJECT BY
IMG IJ350 IntelliJack System BE
(E) FLOOR SHEATHING
(E) FLOOR FRAMING
(E) BEAM
IJ—LR PER GENERAL (4�/2"W MIN)
NOTES (3" MAX
UNBRACED THREADED
ROD LENGTH) IMG IJ—TP PER GENERAL
NOTES W/ (4) #12x3"
WOOD SCREWS
IMG IJ—TC PER
GENERAL NOTES IMG IJ-350 PER
GENERAL NOTES (CUT
To REO'D LENGTH)
IMG IJ—IC PER IMG IJ—BP PER GENERAL
GENERAL NOTES NOTES W/ 5/,"0x41/q"
(E) INTERIOR a EMBED SS SLEEVE ANCHOR
GRADE
W s I II I 111111111 111=
COMPACTED STRUCTURAL
PER FILL PER PLAN
PLAN
Note: Section above is a general representation of intellijack system, refer to plan for layout and project specific details.
IntelliJack System = IJ350
Footing Type= CIP
Pmax= 3.694 kips
Maximum Tube Unbraced Length, dt= 10.000 ft
Maximum Threaded Rod Unbraced Length, dt,= 3.000 in
Eccentricity, en,ax= 1.000 in
Moment= 3.694 in-kips
Tube Properties
Design Tube OD= 3.500 in
Design Wall Thickness= 0.165 in
k= 1.00
r= 1.181 in
A= 1.729 in
c= 1.750 in
S= 1.377 in
1 = 2.409 in
E= 29000 ksi
Fy= 46 ksi
Tube Output
kl/r= 101.65 Slenderness OK
Cc= 111.55
F'e= 14.45 ksi
Fa= 14.06 ksi
fa= 2.14 ksi
Fb= 30.36 ksi
fb= 2.68 ksi
Cm = 1.00
fa/Fa= 0.15 Eq 1-11-1 and Eq 1-11-2
Eq 1-11-1 0.25572 Tube OK
Eq 1-11-2 0.16580 Tube OK
Eq H1-3 NA
Threaded Rod Properties
Threaded Rod Dia. = 1.250 in
k= 1.00
r= 0.313 in
A= 1.227 in
c= 0.625 in
S= 0.192 in
1 = 0.120 in
E= 29000 ksi
Fy= 70 ksi
Threaded Rod Output
kl/r= 9.60 Slenderness OK
Cc= 90.43
F'e= 1619.74 ksi
Fa= 40.79 ksi
fa= 3.01 ksi
Fb= 46.20 ksi
fb= 19.26 ksi
Cm = 1.00
fa/Fa= 0.07 Eq 1-11-3 may be used
Eq H1-1 NA
Eq H1-2 NA
Eq 1-11-3 0.49 Tube OK
Bearing Capacity of Cast-In-Place Footing _
Footing Depth = 6 in
Footing Width = 24 in
Footing Length = 24 in
Soil Bearing Capacity= 1500 psf
Capacity= 6.00 k OK
MAX LOAD TO INTELLIJACK=3694LB
3.5 IN DIAMETER INTELLIJACK TUBE WITH 0.165 IN. THICK WALL AND MAX HEIGHT OF 10FT
1-1/4 IN DIAMETER SOLID THREADED ROD WITH MAX HEIGHT OF 3 IN
24 IN SQR X 6 IN DP STRUCTURAL FILL
EMBED THREADED ROD A MINIMUM OF 314 IN INTO CONFINING RING AND THREADED INSERT
5FA Design Group, LLC
PROJECT NO. SHEET NO.
STRUCTURAL I GEOTECHNICAL I SPECIAL INSPECTIONS IBA22-378
PROJECT DATE
Cameron Residence Floor Support 8/30/2022
SUBJECT BY
IMG IntelliBrace System BE
Lateral Earth Pressure Input Values
Width of Floor Joist= 1.5 in OK, No Add'I Blocking Needei
Add'I Blocking Thickness= N/A in
Spacing,s= 58 in OC
Angle of Internal Soil Friction (Soil on Soil),(D= 30.0 °
Soil Backfill Angle,9= 0.0 °
Height of Grade h9= 5 ft
Height of Wall,hW= 7 ft
Simplified Method Seismic Multiplier, KE= 0
Unit Weight of Earth,we= 110 Ib/ft3
Surcharge Load,ws= 40 Ib/ft2
Lateral Earth Pressure Coefficient, k= 0.333
Active Earth Pressure,wa= 40 Ib/ft3
Lateral Earth Pressures
Seismic Pressure, HE= 0 lb/ft of Wall
Surcharge Pressure, Hsu= 67 lb/ft of Wall
Active Earth Pressure, Ha= 500 lb/ft of Wall
Total Seismic Pressure, HE= 0 lb Applied at 3.34 ft
Total Surcharge Pressure, Hsu= 322 lb Applied at 2.50 ft
Total Active Earth Pressure, Ha= 2417 lb Applied at 1.67 ft
Horizontal Pressure, HT= 567 lb/ft of Wall
Total Horizontal Pressure, HT= 2739 lb Applied at 1.76 ft
l Reactions
Total Force at Base of IntelliBrace, FB= 2048 Ibs
Total Force at Top of IntelliBrace, FE= 690 Ibs
Capacity of 3/4"Thru-Bolts= 1740 Ibs OK
Capacity of Anchor Bolt into Conc Slab= 10200 Ibs OK
T SHEATHING T/SHEATHING
PER ARCH
r R/FRAMING _
l f- � - B T/SHEATHING
II PER ARCH
_I
I IIIII'
III
I—�
T SLAB
I—�
a• III
'=III=III,—II�II .. III
NOTE:SECTION ABOVE IS A GENERAL
REPRESENTATION OF A INTELLBRACE SYSTEM. REFER
TO THE PLAN FOR LAYOUT AND PROJECT SPECIFICS.
Project Title:
Engineer:
Project I D:
Project Descr:
Steel Beam Project File: IBA22-378 Cameron Residence.ec6
LIC#:KVV-06015057,Build:20.21.9.26 SFA ENGINEERING LLC (c)ENERCALC INC 1983-2021
DESCRIPTION: Intellibrace
CODE REFERENCES
Calculations per AISC 360-16, IBC 2018, CBC 2019, ASCE 7-16
Load Combination Set: IBC 2018
Material Properties
Analysis Method Allowable Strength Design Fy: Steel Yield : 50.0 ksi
Beam Bracing : Completely Unbraced E: Modulus: 29,000.0 ksi
Bending Axis: Major Axis Bending
H(2 417) L(O. 220)
S4x7.7
L Span=7.0 ft -I
r �
Applied Loads Service loads entered. Load Factors will be applied for calculations.
Beam self weight NOT internally calculated and added
Load(s)for Span Number 1
Point Load : L= 0.3220 k @ 2.50 ft
Point Load : H =2.417 k @ 1.670 ft
DESIGN SUMMARY •
Maximum Bending Stress Ratio = 0.391 : 1 Maximum Shear Stress Ratio = 0.133 : 1
Section used for this span S4x7.7 Section used for this span S4x7.7
Ma :Applied 3.415 k-ft Va :Applied 2.047 k
Mn/Omega :Allowable 8.733 k-ft Vn/Omega :Allowable 15.440 k
Load Combination +L+H Load Combination +L+H
Location of maximum on span 1.680ft Location of maximum on span 0.000 ft
Span#where maximum occurs Span#1 Span#where maximum occurs Span#1
Maximum Deflection
Max Downward Transient Deflection 0.020 in Ratio= 4,116 —360
Max Upward Transient Deflection 0.000 in Ratio= 0 <360 Span: 1 : L Only
Max Downward Total Deflection 0.135 in Ratio= 620 —240. Span: 1 :+L+H
Max Upward Total Deflection 0.000 in Ratio= 0 <240.0
Vertical Reactions Support notation : Far left is#' Values in KIPS
Load Combination Support 1 Support 2
Overall MAXimum 2.047 0.692
Overall MINimum -0.207 -0.115
H Only 1.840 0.577
+L+H 2.047 0.692
+0.750L+H 1.996 0.663
+0.60H 1.104 0.346
L Only 0.207 0.115