Ventilation, Makeup and Combustion
Air Calculations Submittal Form for New Dwellings
These blank submittal forms and instructions are available on the City of Edina website. The completed form must be submitted at the
time of application for a building and mechanical permit for new construction. Additional forms may be downloaded and printed HERE.
Slte Address 01
Contractor Com leted B leaseprint) SI nature
Section A
Ventilation Quantity
(Determine quantity by using Table R403.5.2 or Equation R403.5.2)
Square feet(Conditioned area including
Basement—finished or unfinished) Total required ventilation
Number of bedrooms Continuous ventilation
Directions-Determine the total and continuous ventilation rate by either using Table R403.5.2 or equation R403.5.2.
The table and equation are below.
Table 11403.5.2
Total and Continuous Ventilation Rates(in cfm)
Number of Bedrooms
1 2 3 4 5 6
Conditioned space Total/ Total/ Total/ Total/ Total/ Total/
(in sq.ft.) continuous continuous continuous continuous continuous continuous
1000-1500 11 60/40 ❑ 75/40 ❑ 90/45 ❑ 105/53 ❑ 120/60 1:1 135/68
1501-2000 1:1 70/40 11 85/43 ❑ 100/50 ❑ 115/58 11 130/65 ❑ 145/73
2001-2500 ❑ 80/40 11 95/48 ❑ 110/55 ❑ 125/63 ❑ 140/70 11 155/78
2501-3000 ❑ 90/45 ❑ 105/53 ❑ 120/60 1:1 135/68 11 150/75 ❑ 165/83
3001-3500 ❑ 100/50 0 115/58 ❑ 130/65 ❑ 145/73 11 160/80 ❑ 175/88
3501-4000 ❑ 110/55 0 125/63 ❑ 140/70 ❑ 155/78 ❑ 170/85 11 185/93
4001-4500 ❑ 120/60 0 135/68 11 150/75 11 165/83 4 180/90 ❑ 195/98
4501-5000 ❑ 130/65 1:1 145/73 1-1 160/80 ❑ 175/88 ❑ 190/95 ❑ 205/103
5001-5500 ❑ 140/70 ❑ 155/78 13 170/85 11 185/93 1:1 200/100 ❑ 215/108
5501-6000 1:1 150/75 0 165/83 0 180/90 ❑ 195/98 0 210/105 0 225/113
Equation R403.5.2
(0.02 x square feet of conditioned space)+[15 x(number of bedrooms+1)]=Total ventilation rate(cfm)
Total ventilation—The mechanical ventilation system shall provide sufficient outdoor air to equal the total ventilation rate
average,for each one-hour period according to the above table or equation. For heat recovery ventilators(HRV)and energy
recovery ventilators(ERV)the average hourly ventilation capacity must be determined in consideration of any reduction of
exhaust or out outdoor air intake,or both,for defrost or other equipment cycling.
Continuous ventilation-A minimum of 50 percent of the total ventilation rate,but not less than 40 cfm,shall be provided,
on a continuous rate average for each one-hour period. The portion of the mechanical ventilation system intended to be
continuous may have automatic cycling controls providing the average flow rate for each hour is met.
I:\Building\SafetyPolicieslnformation\EdinaExtrasServer\Docx's\RESIDENTIAL SD05 VENTILATION MAKEUP AND COMBUSTION AIR CALCS.pdf