SCOPE OF WORK:
These drawings apply to the construction of cast-in-place concrete foundation walls for typical residential
cases. These drawings are not to scale and all conditions are to be verified by the contractor. Means and
methods of construction for shoring, water-proofing, insulation, flashing, control and construction joints,
and all other non-structural requirements are to be by others in accordance with the Code and standard
industry practice. These drawings are valid until the end of 2022.
The drawings are to only be used by the contractor noted below or his authorized sub-contractors/clients.
These drawings are to be provided to the building inspection department as part of the permit package.
INDEX:
S1 - Scope, Index, and Certification
S2-General Notes
S3- Step Footing Detail
S4- Frost Wall Detail
S5- Lookout Wall Detail
S6- Full Height Wall Detail
MATERIALS:
Reinforcing Steel:Grade 40 (40 ksi)for#4 and smaller bars
Grade 60 (60 ksi)for#5 bars and larger
Rebar Substitution Notes:
1. Two#4's bundled may be used to substitute (1)#6 and vice versa provided they are of the same grade steel.
2. For vertical bars on S6,#5's may be used in lieu of#6's at two-thirds of the noted spacing.
Concrete: Mix design is to be prepared by the concrete supplier to meet the project's requirements
Minimum 28 day compressive strength of 3000 psi for walls
Minimum 28 day compressive strength of 5000 psi for footings
Footings may be 3000 psi if an approved admixture is used to achieve a water and vapor
resistance equivalent to 5000 psi
Backfill Soil: Sand-30 psf/ft effective lateral pressure
Sandy Clay (SC)-45 psf/ft effective lateral pressure
Clay-60 psf/ft effective lateral pressure
hereby certify that this plan,specification,or
SITE ADDRESS: report was prepared by me or under my direct
supervision and that I am a duly licensed
professional engineer under the laws of the state
Street: of Minnesota.
City:
State: MN Zip: Craig Oswell, PE(MN#42341)
1/1/2022
Oswell Engineering and Consulting, L.L.C. 1901 E Hennepin Ave,#201
Project Name: 2022 Standardized Concrete Foundation Drawings Minneapolis, MN 55413
Description: Scope of Work, Index, and Certification Phone: 612-720-4639
Project# 21.100 Fax: 612-886-2966
Client Name: Abfalter Brothers Concrete LLC www.oswellec.com
Client Address: 15546 Cleveland Street, Elk River, MN 55330 Page S1 of S6
GENERAL NOTES:
1. Wall thicknesses noted are nominal unless specifically stated otherwise.
2. Maximum wall to footing centerline offset is 2". A minimum of 2"of footing is to extend on each side of the wall.
3. Bar laps when required are to be at least 40 bar diameters for grade 40 and 60 bar diameters for grade 60.
4. Bend horizontal bars or provide matching hooks around all wall corners and intersections.
5. Horizontal bars may be placed anywhere within the wall thickness provided 2"minimum cover is provided.
6. Allowable bar placement tolerance is 1/2". Tying is not required if tolerances are met and maintained.
7. Dowels may be drilled and installed after footing pour unless otherwise noted. Vertical bars may be embedded
into footing in place of dowels at the same embedment. Vertical bars and dowels do not need to align. Dowels
may be bent down for safety and covering then bent back before wall placement.
8. Sill plate sections require at least two anchors with one within 4"to 12"of each end and at all corners and
intersections. Walls less than 24" in length require only one anchor. Sill plates may overhang the face of the wall
provided the overhang is not loaded vertically and all anchor bolt/connection tolerances are met.
9. Anchor bolts 1/2"or larger in diameter do not require corrosion protection per IRC section R317.3.1 exception 1.
10. Anchor bolts may be substituted with 1/2"diameter threaded rod epoxy grouted at same spacing with 7"embed.
11. The presence of form oil on the reinforcing is acceptable for the conditions contained in these drawings.
12. Slope grade 6"minimum downward away from foundations within first 10 feet or provide Code adequate swale.
13. Do not backfill until the concrete has reached at least 70 percent of the 28 day concrete strength. Use of
adequate shoring is required when the final floor and slab systems are not in place and fully anchored.
14. Maximum inside window well dimension is 72". Well walls are to be at least 8"thick placed monolithically with
house walls with horizontal bars extended into them and around corners. Provide two additional vertical bars and
one additional anchor bolt each side of opening. Opening header by others.
COLD WEATHER GUIDELINES:
The following information is general guidelines for the placement of concrete in cold weather conditions. It is the
contractor's responsibility to ensure proper means and methods are followed and that the final in place product is
adequate.
1. The contractor is to work with the concrete supplier to obtain a mix design which accounts for the conditions
expected. Use of extra cement, early-strength concrete,and accelerators are recommended at temperatures
below 20 degrees F.
2. Concrete is to be delivered to the site in a timely manner.
3. Placement of concrete earlier in the day to take advantage of latent heat of sunlight is advised.
4. Do not add additional water. Using water-reducing admixtures is recommended when required.
5. Forms are to be free of snow and ice. Do not place concrete in contact with frozen ground, snow,or ice.
6. Preheating of rebar is not required, however it is to be free of frost,snow,and ice.
7. Use of form blankets or other approved protection is highly recommended for the top of the wall at temperatures
below 10 degrees F and for the whole wall when below zero degrees F.
Oswell Engineering and Consulting, L.L.C. 1901 E Hennepin Ave,#201
Project Name: 2022 Standardized Concrete Foundation Drawings Minneapolis, MN 55413
Description: General Notes Phone: 612-720-4639
Project# 21.100 Fax: 612-886-2966
Client Name: Abfalter Brothers Concrete LLC www.oswellec.com
Client Address: 15546 Cleveland Street, Elk River, MN 55330 Page S2 of S6
1/1/2022
Adjacent steps are to be
placed no closer to either side
of the beam section than twice
6'-0"maximum ste the height of the largest step
(beam section) Optional control joint each end
of beam section by others
(2)bundled#4 horizontal bars
top&bottom w/3"min
clearance extended at least
24"minimum beyond each end
Maximum applied c of beam section (bar length=
actual load=4000 plf E
uniform or 12,000 - step height+4')
pound concentrated a 6"minimum thick cast-in-place
concrete foundation wall
I HIGH FOOTING
I
i
i
i
i
i
i
i
High footing should be placed
i
at 1-to-1 (45 degree) line, if
LOW FOOTING �� high footing is closer to step
i than this line,place beam
section rebar as if it was at
this line as shown
FOOTING STEP DETAIL
Oswell Engineering and Consulting, L.L.C. 1901 E Hennepin Ave,#201
Project Name: 2022 Standardized Concrete Foundation Drawings Minneapolis, MN 55413
Description: Step Footing Detail(NOT TO SCALE) Phone: 612-720-4639
Project# 21.100 Fax: 612-886-2966
Client Name: Abfalter Brothers Concrete LLC www.oswellec.com
Client Address: 15546 Cleveland Street, Elk River, MN 55330 Page S3 of S6
1/1/2022
Wall framing by others
Sill plate by others w/1/2"
diameter anchor bolts w/7"
minimum embed&standard
washers @ 72"o.c. max or
Optional slab ledge,maximum equivalent metal strap anchors
stem height is 12"w/width to (Anchor bolt clearance between
match sill plate edge of both wall and sill plate is
to be 2")
Grade to be at least 6"below top
-E of wall
•
(1)#4 continuous horizontal bar
w/in 18"of top of wall
6"minimum thick cast-in-place
concrete wall
#4 x 2'-0"long dowels @ 72"o.c.
max w/5"minimum embed
Unreinforced concrete strip
footing per Code by others,
provide frost protection per Code
as required
WALKOUT/ SLAB-ON-GRADE FROST WALL DETAIL
Note: Maximum unbalanced fill height is 36"for 8"thick wall&48"for 10"wall
Oswell Engineering and Consulting, L.L.C. 1901 E Hennepin Ave,#201
Project Name: 2022 Standardized Concrete Foundation Drawings Minneapolis, MN 55413
Description: Frost Wall Detail(NOT TO SCALE) Phone:612-720-4639
Project# 21.100 Fax: 612-886-2966
Client Name: Abfalter Brothers Concrete LLC www.oswellec.com
Client Address: 15546 Cleveland Street, Elk River, MN 55330 Page S4 of S6
1/1/2022
Wall framing by others
Sill plate by others w/1/2"
diameter anchor bolts w/7"
minimum embed&standard
washers @ 72"o.c. max or
equivalent metal strap anchors
(Anchor bolt clearance between
edge of both wall and sill plate is
to be 2")
Grade to be at least 6"below top
of wall
(1)#4 continuous horizontal bar
w/in 18"of top of wall
E6"minimum thick cast-in-place
concrete wall
N
M
#4 x 2'-0"long centered
dowels w/5"minimum embed
wet set or epoxy grouted in Footing elevation may vary below
place slab,provide frost protection per
6"wall spacing_ Code
32"o.c. max for sand&24" 8"thick x 18"wide minimum
o.c. max for SC&clay unreinforced concrete strip
8"+wall spacing: footing(16"wide minimum for
48"o.c. max for sand,42"o.c. maximum unbalanced grade of 2'-
max for SC,&36"o.c. max for 6"or less), larger footing width
clay may be required for specific soil
bearing conditions to be
determined per Code by others
LOOKOUT WALL DETAIL
Oswell Engineering and Consulting, L.L.C. 1901 E Hennepin Ave,#201
Project Name: 2022 Standardized Concrete Foundation Drawings Minneapolis, MN 55413
Description: Lookout Wall Detail(NOT TO SCALE) Phone:612-720-4639
Project# 21.100 Fax: 612-886-2966
Client Name: Abfalter Brothers Concrete LLC www.oswellec.com
Client Address: 15546 Cleveland Street, Elk River, MN 55330 Page S5 of S6
1/1/2022
/Wood floor&wall framing by others
Connection of floor members to sill plate
to be per Code by others
2x6 minimum sill plate w/1/2"diameter
anchor bolts w/7"minimum embed&2"
/ wide x 1/8"thick square or round
countersunk washers or alternative
anchor(Anchor bolt clearance between
• edge of both wall and sill plate is to be
2.5")(see table below for spacing)
Grade to be at least 6"below top of wall
Exterior top of wall may have a brick
ledge provided the stem wall formed is
at least 6"thick&no more than 16"high
Continuous#4 horizontal bars,provide
at least(2)@ 8'-0"clear,(3)@ 9'-0"
d clear,&(4)@ 10'-0"clear,At
= contractor's option: The lowest wall
horizontal bar may be omitted if(2)#4
U continuous horizontal bars are placed in
the footing
Cast-in-place concrete foundation wall
w/#6 or equivalent vertical bars placed
1.5"from inside face,see table below for
spacing
#4 x 2'-0"long dowels @ 72"o.c.max w/
5"minimum embed
Unreinforced concrete strip footing per
Code by others,elevation below slab
may vary as required
BASEMENT WALL DETAIL
Clear Height and Soil Type Table Notes:
Wall 8'or Less 1 9' 1 10, (1)= Unreinforced if concrete is 4000 psi or if
Thickness rN
nd SC Clay Sand SC Clay Sand SC Clay clear height is 4"less
Vertical Reber Spacing (2)= Unreinforced if concrete is 5000 psi or if
8" A NA 136"(11 NA 36"(2) 36" 36"(1 36" 24" clear height is 4"less
10" NA NA NA I NA I NA 36"(1 NA 36"(1 36" Allowed alternate anchors are:
12" NA NA NA I NA I NA I NA I NA NA NA MAB/ST,MASA/FA3, FWAZ,or 1/2"
Sill Anchor Spacing diameter expansion bolts w/6"min embed
Bolts 72" 72" 48" 72" 48" 36" 60" 36" 24" (install in accordance with the
Alternate 1 48" 24" 18" 36" 18" 12" 24" 12" 8., manufacturer's recommendations)
Oswell Engineering and Consulting, L.L.C. 1901 E Hennepin Ave,#201
Project Name: 2022 Standardized Concrete Foundation Drawings Minneapolis,MN 55413
Description: Full Height Wall Detail(NOT TO SCALE) Phone:612-720-4639
Project# 21.100 Fax:612-886-2966
Client Name: Abfalter Brothers Concrete LLC www.oswellec.com
Client Address: 15546 Cleveland Street,Elk River,MN 55330 Page S6 of S6