HomeMy WebLinkAboutFinal Engineered garage repair 126 Christenson CT Address:
126 Christenson Court NE
Fridley, MN 55432
SAFE HAVEN SE
v� ' ;��j��Nr�FL �._ 4852 38THH AVENUE SOUTH
STRUCTURAL ENGINEERING MINNEAPOLIS, MN 55417
6 1 2-284-7033
July 11, 2023
SMC Construction, Inc APPROVED
Sinan Music JensenD09/19/2023
Project (SH#23503): Garage Damage 126 Christenson Ct NE This plan copy to be at job site
Fridley, MN
Dear Sinan: SEPARATE PERMITS FOR: ELECT, PLUMB. MECH.
As you requested, I have reviewed the damage caused by a car crashing into the garage located at
126 Christenson Court Northeast in Fridley, Minnesota. A site visit was conducted by Derek Phillips,
PE on July 10, 2023. The vehicle ran into the northwest side of the garage and will need to be
repaired. The following items should be addressed:
• The top of the concrete stem wall was damaged and will need to be replaced. The cracked
section runs approximately 8'-0" in length. This area shall be removed and a new stem wall
shall be poured. Install new 1/2" diameter threaded rods at 2'-0" on center. Epoxy anchored
the rods 6" minimum into the good concrete and apply a bonding agent prior to pouring the
new stem wall. This will also act as the anchor bolts for the stud wall above.
• Install a new treated 2x4 sill plate along this wall as needed. Approximately 10'-0" in length.
• The 2x4 stud wall spaced at 16" on center with a (2) 2x4 top plate shall be rebuilt in this area.
Push all the garage walls back into plumb as needed. A temporary wall will need to be built
along this wall to support the garage attic trusses during construction.
• The sheathing and siding in this area will need to be replaced. Fasten sheathing to wall stud
with 8d nails at 6" on center along the edges and 12" on center at the intermediate studs,
minimum. Fasten siding per code.
• The brick veener half wall along the northeast wall and around the corner to the garage door
will need to be replaced.
• During construction, verify that the attic trusses along the northeast wall are not damaged.
This was not visible at time of inspection but the ceiling should be opened up to verify that the
ends of the trusses are intact. Patch ceiling sheet rock as needed afterwards.
The 2020 Minnesota State Residential Code is applicable. Please call me if you have any questions
concerning this project.
Sincerely, I hereby certify that this plan,specification or report was
prepared by me or under my direct supervision and that I
am a duly Licensed Professional Engineer under the laws
. of the State of Minnesota.
Signature:
/�Z&l
Derek O Phillips, P.E. Printed Name: Derek O Phillips
Safe Haven Structural Engineering LLC Date: 7/11/23 MN Reg. No.: 47507
DISCLAIMER: The structural evaluation is limited to structural elements judged to represent typical framing element conditions and capacities.
The opinions stated in this letter are based on Safe Haven SE's reasonable professional judgment and experience. This letter does not
address any other portion of the structure other than those mentioned,nor does it provide any warranty,either expressed or implied,for any
portion of the existing structure.