HomeMy WebLinkAboutSolar By Us_Safdar Ali Haideri Letter SS VECTOR
E n G I n E E R S
VSE Project Number:U3507.0297.231
November 8,2023
TruNorth Solar LLC
ATTENTION: Donna Pickard
3735 Dunlap St.N.
Arden Hills,MN 55112
REFERENCE: Solar By Us_Safdar Ali Haideri Residence: 1133 Fireside Drive,Fridley,MN 55432
Solar Array Installation
To Whom It May Concern:
We have reviewed the existing structure at the above referenced site. The purpose of our review was to determine the
adequacy of the existing structure to support the proposed installation of solar panels on the roof as shown on the panel
layout plan.
Based upon our review,we conclude that the existing structure is adequate to support the proposed solar panel installation.
Design Parameters
Code: 2020 Minnesota Residential Code(2018 IRC)
Risk Category:II
Design wind speed,Vult: 115 mph(3-sec gust)
Wind exposure category: C
Ground snow load,Pg: 50 psf
Existing Roof Structure
Roof structure: 2x6 rafters @ 16" o.c.
Roof pitch: 3:12
Connection to Roof
Mounting connection: (1)5/16" lag screw w/min.2.5"threaded embedment into framing at max.48" o.c.along rails
Install(2)rails per row of panels,evenly spaced;panel length perpendicular to the rails shall not exceed 74 in
Rail cantilever shall not exceed the lesser of 50%of the connection spacing or maximum cantilever allowed by
manufacturer
Connections shall be staggered so as not to overload any existing structural member
Conclusions
Based upon our review, we conclude that the existing structure is adequate to support the proposed solar panel installation.
The glass surface of the solar panels allows for a lower slope factor per ASCE 7, resulting in reduced design snow load on
the panels. The gravity loads, and thus the stresses of the structural elements, in the area of the solar array are either
decreased or increased by no more than 5%. Stress decreases or increases of no more than 5% are considered acceptable.
Therefore,the structure is permitted to remain unaltered.
651 W. Galena Park Blvd.,Ste. 101/Draper, UT 84020/T(801)990-1775/F(801)990-1776/www.vectorse.com
VSE Project Number: U3507.0297.231
Solar By Us_Safdar Ali Haideri Residence
YE C T O R 11,8,2023
E M G I n E E R S 0
The solar array will be flush-mounted (no more than 10" above the roof surface) and parallel to the roof surface. Thus, we
conclude that any additional wind loading on the structure related to the addition of the proposed solar array is negligible.
The attached calculations verify the capacity of the connections of the solar array to the existing roof against wind (uplift),
the governing load case. Increases in lateral forces less than 10% are considered acceptable. Thus the existing lateral force
resisting system is permitted to remain unaltered.
Limitations
Installation of the solar panels must be performed in accordance with manufacturer recommendations. All work performed
must be in accordance with accepted industry-wide methods and applicable safety standards. The contractor must notify
Vector Structural Engineering, LLC should any damage, deterioration or discrepancies between the as-built condition of the
structure and the condition described in this letter be found. The use of solar panel support span tables provided by others is
allowed only where the building type, site conditions, site-specific design parameters, and solar panel configuration match
the description of the span tables.The design of the solar panels, solar racking(mounts,rails, etc.)and electrical engineering
is the responsibility of others. Waterproofing around the roof penetrations is the responsibility of others. Vector Structural
Engineering assumes no responsibility for improper installation of the solar array. Vector Structural Engineering shall be
notified of any changes from the approved layout prior to installation.
VECTOR STRUCTURAL ENGINEERING,LLC
LICENSED
�. PROFESSIONAL .
ENGINEER —
11/08/2023
Brett Veazie,P.E. I hereby certify that this plan,specification or report was prepared
Project Engineer by me or under my direct supervision and that I am a duly Licensed
Professional Fngineer under the laws of the State of Mnnesota.
Enclosures Brett Veazie,License No.56392,
Expiration Date:30-June-2024
BDV/shs
651 W. Galena Park Blvd.,Ste. 101/Draper, UT 84020/T(801)990-1775/F(801)990-1776/www.vectorse.com
JOB NO.: U3507.0297.231
YETO R ® SUBJECT: WIND PRESSURE
n G I n E E R S
PROJECT: Solar By Us_Safdar Ali Haideri Residence
Com onents and Cladding Wind Calculations
Label: Isolar Panel Array Note: Calculations per ASCE 7-10
SITE-SPECIFIC WIND PARAMETERS:
Basic Wind Speed [mph]: 115 Notes:
Exposure Category: C
Risk Category: II
ADDITIONAL INPUT & CALCULATIONS:
Height of Roof, h [ft]: 15 (Approximate) Hip?
Comp/Cladding Location: Gable/Hip Roofs 7°<0 <_ 27° No
Enclosure Classification: Enclosed Buildings
Zone 1 GCp: 0.9 Figure 30.4-213 (enter negative pressure coefficients)
Zone 2 GCp: 1.7
Zone 3 GCp: 2.5
a: 9.5 Table 26.9-1
z9 [ft]: 900 Table 26.9-1
Kh: 0.85 Table 30.3-1
KZt: 1 Equation 26.8-1
Kd: 0.85 Table 26.6-1
Velocity Pressure, qh [psf]: 24.4 Equation 30.3-1
GCp;: 0 Table 26.11-1
PRESSURES: p = q, GCp — GCpi Equation 30.9-1
Zone 1, p [psf]: 21.8 psf (1.0 W, Interior Zones, beyond 'a' from roof edge)
Zone 2, p [psf]: 40.4 psf (1.0 W, End Zones, within 'a' from roof edge)
Zone 3, p [psf]: 62.2 psf (1.0 W, Corner Zones, within 'a' from roof corner)
(a= 3 ft)
JOB NO.: U3507.0297.231
YETO R p SUBJECT: CONNECTION
n G I n E E R S
PROJECT: Solar By Us_Safdar Ali Haideri Residence
Calculate Uplift Forces on Connection
Pressure 1 Max Trib. Max Uplift
Width
(0.6 Dead -0.6 Wind) Max Trib. Area 2 Force
(psf) (ft) (ft2) (Ibs)
Zone 1 11.3 4.0 12.3 139
Zone 2 22.5 4.0 12.3 277
Zone 3 35.5 4.0 12.3 438
Calculate Connection Capacity
Lag Screw Size [in]: 5/16
Cd: 1.6 NDS Table 2.3.2
Embedment3 [in]: 2.5
Grade: SPF (G = 0.42)
Nominal Capacity [Ibs/in]: 205 NDS Table 12.2A
Number of Screws: 1
Prying Coefficient: 1.4
Total Capacity [Ibs]: 586
Determine Result
Maximum Demand [lbs]:l 438
Lag Screw Capacity [Ibs]:1 586
Result: Capacity > Demand, Connection is adequate.
Notes
1. 'Max Trib. Width' is the width along the rails tributary to the connection.
2. 'Max Trib Area' is the product of the 'Max.Trib Width' and 1/2 the panel width/height perpendicular to the
rails. (2) rails per row of panels. Length of panels perpendicular to the rails shall not exceed 74".
3. Embedment is measured from the top of the framing member to the beginning of the tapered tip of the lag
screw. Embedment in sheathing or other material is not effective.The length of the tapered tip is not part of the
embedment length.
JOB NO.: U3507.0297.231
YET O R p SUBJECT: GRAVITY LOADS
n G I n E E R S
PROJECT: Solar By Us_Safdar Ali Haideri Residence
GRAVITY LOADS Roof Pitch: 3.0 :12
Design material Increase due to Material weight
ROOF DEAD LOAD (D) weight [psf] pitch [psf]
Composite Shingles 2.1 1.03 2.0
1/2" Plywood 1.0 1.03 1.0
Framing 3.0 3.0
Insulation 0.0 0.0
1/2" Gypsum Clg. 0.0 1.03 0.0
M, E & Misc 0.0 0.0
Total Existing Roof DL 6.1
PV Array DL 3.1 1.03 3
ROOF LIVE LOAD (Lr)
Existing Design Roof Live Load [psf] 20 ASCE 7-16 Table 4.3-1
Roof Live Load With PV Array [psf] 0 2020 MRC, Section R324.4.1.1
SNOW LOAD (S): Existing w/ Solar Array
Roof Slope [x:12]: 3.0 3.0
Roof Slope [°]: 14 14
Ground Snow Load, pg [psf]: 50 50 ASCE 7-16, Section 7.2
Terrain Category: C C ASCE 7-16, Table 7.3-1
Exposure of Roof: Fully Exposed Fully Exposed ASCE 7-16, Table 7.3-1
Exposure Factor, Ce: 0.9 0.9 ASCE 7-16, Table 7.3-1
Thermal Factor, Ct: 1.1 1.1 ASCE 7-16, Table 7.3-2
Risk Category: 11 II ASCE 7-16, Table 1.5-1
Importance Factor, Is: 1.0 1.0 ASCE 7-16, Table 1.5-2
Flat Roof Snow Load, pf [psf]: 35 35 ASCE 7-16, Equation 7.3-1
Minimum Roof Snow Load, pm [psf]: 20 20 ASCE 7-16, Section 7.3.4
Unobstructed Slippery Surface? No Yes ASCE 7-16, Section 7.4
Slope Factor Figure: Figure 7-2b Figure 7-2b ASCE 7-16, Section 7.4
Roof Slope Factor, Cs: 1.00 0.93 ASCE 7-16, Figure 7.4-1
Sloped Roof Snow Load, Ps [psf]: 35 32 ASCE 7-16, Equation 7.4-1
Design Snow Load, S [psf]: 35 32
JOB NO.: U3507.0297.231
TO R® SUBJECT: LOAD COMPARISON
E n G I n E E R S
PROJECT: Solar By Us_Safdar Ali Haideri Residence
Summary of Loads
Existing With PV Array
D [psf] 6 9
Lr [psf] 20 0
S [psf] 35 32
Maximum Gravity Loads:
Existing With PV Array
(D+ Lr)/Cd [psf] 21 10 ASCE 7-16, Section 2.4.1
(D +S)/Cd [psf] 35 36 �ASCE 7-16, Section 2.4.1
(Cd=Load Duration Factor=0.9 for D,1.15 for S,and 1.25 for Lr)
Maximum Gravity Load [psf]:1 35 1 36
Ratio Proposed Loading to Current Loading: 1 102% OK
The gravity loads, and thus the stresses of the structural elements, in the area of the
solar array are either decreased or increased by no more than 5%. Stress decreases or
increases of no more than 5%are considered acceptable.Therefore,the structure is
permitted to remain unaltered.