Final Solar review 1130 Fireside Drive
VECTOR APPROVED JensenDll/20/2023 E n G I n E E R S VSE Project Number:U3507.0297.231 November 8,2023 SEPARATE PERMITS FOR: ELECT TruNorth Solar LLC ATTENTION: Donna Pickard 3735 Dunlap St.N. Arden Hills,MN 55112 REFERENCE: Solar By Us_Safdar Ali Haideri Residence: 1133 Fireside Drive,Fridley,MN 55432 Solar Array Installation To Whom It May Concern: We have reviewed the existing structure at the above referenced site. The purpose of our review was to determine the adequacy of the existing structure to support the proposed installation of solar panels on the roof as shown on the panel layout plan. Based upon our review,we conclude that the existing structure is adequate to support the proposed solar panel installation. Design Parameters Code: 2020 Minnesota Residential Code(2018 IRC) Risk Category:II Design wind speed,Vult: 115 mph(3-sec gust) Wind exposure category: C Ground snow load,Pg: 50 psf Existing Roof Structure Roof structure: 2x6 rafters @ 16" o.c. Roof pitch: 3:12 Connection to Roof Mounting connection: (1)5/16" lag screw w/min.2.5"threaded embedment into framing at max.48" o.c.along rails Install(2)rails per row of panels,evenly spaced;panel length perpendicular to the rails shall not exceed 74 in Rail cantilever shall not exceed the lesser of 50%of the connection spacing or maximum cantilever allowed by manufacturer Connections shall be staggered so as not to overload any existing structural member Conclusions Based upon our review, we conclude that the existing structure is adequate to support the proposed solar panel installation. The glass surface of the solar panels allows for a lower slope factor per ASCE 7, resulting in reduced design snow load on the panels. The gravity loads, and thus the stresses of the structural elements, in the area of the solar array are either decreased or increased by no more than 5%. Stress decreases or increases of no more than 5% are considered acceptable. Therefore,the structure is permitted to remain unaltered. 651 W. Galena Park Blvd.,Ste. 101/Draper, UT 84020/T(801)990-1775/F(801)990-1776/www.vectorse.com VSE Project Number: U3507.0297.231 Solar By Us_Safdar Ali Haideri Residence YE C T O R 11,8,2023 E M G I n E E R S 0 The solar array will be flush-mounted (no more than 10" above the roof surface) and parallel to the roof surface. Thus, we conclude that any additional wind loading on the structure related to the addition of the proposed solar array is negligible. The attached calculations verify the capacity of the connections of the solar array to the existing roof against wind (uplift), the governing load case. Increases in lateral forces less than 10% are considered acceptable. Thus the existing lateral force resisting system is permitted to remain unaltered. Limitations Installation of the solar panels must be performed in accordance with manufacturer recommendations. All work performed must be in accordance with accepted industry-wide methods and applicable safety standards. The contractor must notify Vector Structural Engineering, LLC should any damage, deterioration or discrepancies between the as-built condition of the structure and the condition described in this letter be found. The use of solar panel support span tables provided by others is allowed only where the building type, site conditions, site-specific design parameters, and solar panel configuration match the description of the span tables.The design of the solar panels, solar racking(mounts,rails, etc.)and electrical engineering is the responsibility of others. Waterproofing around the roof penetrations is the responsibility of others. Vector Structural Engineering assumes no responsibility for improper installation of the solar array. Vector Structural Engineering shall be notified of any changes from the approved layout prior to installation. VECTOR STRUCTURAL ENGINEERING,LLC LICENSED �. PROFESSIONAL . ENGINEER — 11/08/2023 Brett Veazie,P.E. I hereby certify that this plan,specification or report was prepared Project Engineer by me or under my direct supervision and that I am a duly Licensed Professional Fngineer under the laws of the State of Mnnesota. Enclosures Brett Veazie,License No.56392, Expiration Date:30-June-2024 BDV/shs 651 W. Galena Park Blvd.,Ste. 101/Draper, UT 84020/T(801)990-1775/F(801)990-1776/www.vectorse.com JOB NO.: U3507.0297.231 YETO R ® SUBJECT: WIND PRESSURE n G I n E E R S PROJECT: Solar By Us_Safdar Ali Haideri Residence Com onents and Cladding Wind Calculations Label: Isolar Panel Array Note: Calculations per ASCE 7-10 SITE-SPECIFIC WIND PARAMETERS: Basic Wind Speed [mph]: 115 Notes: Exposure Category: C Risk Category: II ADDITIONAL INPUT & CALCULATIONS: Height of Roof, h [ft]: 15 (Approximate) Hip? Comp/Cladding Location: Gable/Hip Roofs 7°<0 <_ 27° No Enclosure Classification: Enclosed Buildings Zone 1 GCp: 0.9 Figure 30.4-213 (enter negative pressure coefficients) Zone 2 GCp: 1.7 Zone 3 GCp: 2.5 a: 9.5 Table 26.9-1 z9 [ft]: 900 Table 26.9-1 Kh: 0.85 Table 30.3-1 KZt: 1 Equation 26.8-1 Kd: 0.85 Table 26.6-1 Velocity Pressure, qh [psf]: 24.4 Equation 30.3-1 GCp;: 0 Table 26.11-1 PRESSURES: p = q, GCp — GCpi Equation 30.9-1 Zone 1, p [psf]: 21.8 psf (1.0 W, Interior Zones, beyond 'a' from roof edge) Zone 2, p [psf]: 40.4 psf (1.0 W, End Zones, within 'a' from roof edge) Zone 3, p [psf]: 62.2 psf (1.0 W, Corner Zones, within 'a' from roof corner) (a= 3 ft) JOB NO.: U3507.0297.231 YETO R p SUBJECT: CONNECTION n G I n E E R S PROJECT: Solar By Us_Safdar Ali Haideri Residence Calculate Uplift Forces on Connection Pressure 1 Max Trib. Max Uplift Width (0.6 Dead -0.6 Wind) Max Trib. Area 2 Force (psf) (ft) (ft2) (Ibs) Zone 1 11.3 4.0 12.3 139 Zone 2 22.5 4.0 12.3 277 Zone 3 35.5 4.0 12.3 438 Calculate Connection Capacity Lag Screw Size [in]: 5/16 Cd: 1.6 NDS Table 2.3.2 Embedment3 [in]: 2.5 Grade: SPF (G = 0.42) Nominal Capacity [Ibs/in]: 205 NDS Table 12.2A Number of Screws: 1 Prying Coefficient: 1.4 Total Capacity [Ibs]: 586 Determine Result Maximum Demand [lbs]:l 438 Lag Screw Capacity [Ibs]:1 586 Result: Capacity > Demand, Connection is adequate. Notes 1. 'Max Trib. Width' is the width along the rails tributary to the connection. 2. 'Max Trib Area' is the product of the 'Max.Trib Width' and 1/2 the panel width/height perpendicular to the rails. (2) rails per row of panels. Length of panels perpendicular to the rails shall not exceed 74". 3. Embedment is measured from the top of the framing member to the beginning of the tapered tip of the lag screw. Embedment in sheathing or other material is not effective.The length of the tapered tip is not part of the embedment length. JOB NO.: U3507.0297.231 YET O R p SUBJECT: GRAVITY LOADS n G I n E E R S PROJECT: Solar By Us_Safdar Ali Haideri Residence GRAVITY LOADS Roof Pitch: 3.0 :12 Design material Increase due to Material weight ROOF DEAD LOAD (D) weight [psf] pitch [psf] Composite Shingles 2.1 1.03 2.0 1/2" Plywood 1.0 1.03 1.0 Framing 3.0 3.0 Insulation 0.0 0.0 1/2" Gypsum Clg. 0.0 1.03 0.0 M, E & Misc 0.0 0.0 Total Existing Roof DL 6.1 PV Array DL 3.1 1.03 3 ROOF LIVE LOAD (Lr) Existing Design Roof Live Load [psf] 20 ASCE 7-16 Table 4.3-1 Roof Live Load With PV Array [psf] 0 2020 MRC, Section R324.4.1.1 SNOW LOAD (S): Existing w/ Solar Array Roof Slope [x:12]: 3.0 3.0 Roof Slope [°]: 14 14 Ground Snow Load, pg [psf]: 50 50 ASCE 7-16, Section 7.2 Terrain Category: C C ASCE 7-16, Table 7.3-1 Exposure of Roof: Fully Exposed Fully Exposed ASCE 7-16, Table 7.3-1 Exposure Factor, Ce: 0.9 0.9 ASCE 7-16, Table 7.3-1 Thermal Factor, Ct: 1.1 1.1 ASCE 7-16, Table 7.3-2 Risk Category: 11 II ASCE 7-16, Table 1.5-1 Importance Factor, Is: 1.0 1.0 ASCE 7-16, Table 1.5-2 Flat Roof Snow Load, pf [psf]: 35 35 ASCE 7-16, Equation 7.3-1 Minimum Roof Snow Load, pm [psf]: 20 20 ASCE 7-16, Section 7.3.4 Unobstructed Slippery Surface? No Yes ASCE 7-16, Section 7.4 Slope Factor Figure: Figure 7-2b Figure 7-2b ASCE 7-16, Section 7.4 Roof Slope Factor, Cs: 1.00 0.93 ASCE 7-16, Figure 7.4-1 Sloped Roof Snow Load, Ps [psf]: 35 32 ASCE 7-16, Equation 7.4-1 Design Snow Load, S [psf]: 35 32 JOB NO.: U3507.0297.231 TO R® SUBJECT: LOAD COMPARISON E n G I n E E R S PROJECT: Solar By Us_Safdar Ali Haideri Residence Summary of Loads Existing With PV Array D [psf] 6 9 Lr [psf] 20 0 S [psf] 35 32 Maximum Gravity Loads: Existing With PV Array (D+ Lr)/Cd [psf] 21 10 ASCE 7-16, Section 2.4.1 (D +S)/Cd [psf] 35 36 �ASCE 7-16, Section 2.4.1 (Cd=Load Duration Factor=0.9 for D,1.15 for S,and 1.25 for Lr) Maximum Gravity Load [psf]:1 35 1 36 Ratio Proposed Loading to Current Loading: 1 102% OK The gravity loads, and thus the stresses of the structural elements, in the area of the solar array are either decreased or increased by no more than 5%. Stress decreases or increases of no more than 5%are considered acceptable.Therefore,the structure is permitted to remain unaltered. smar By Us_safdarAli Haider)c*12528051 /lam IRONRIDGE pitched— 28357 INDUSTRIAL BLVD.,HAY—D,CA 94545 Project Details This plan copy to be at job site Name Solar By Us_Safdar Ali Haideri Date 11/06/2023 Location 1133 Fireside Drive, Fridley, MN 55432 Total modules 16 Module Hanwha Q.Cells:Q.PEAK DUO BLK ML-G10+405(32mm) Total watts 6,480 Dimensions Dimensions:73.98"x 41.14"x 1.26"(1879.0mm x 1045.Omm x 32.Omm) Attachments 28 ASCE 7-16 Rails per row 2 Setback at ridge perR324.6.2 2020 '"w4mft _ ri'7 m ' Roof access and path ' 'ys per R324.6 Ksbc.,d Imagery-23 Ai•bus 'erms ke0o2ama -, System Weight Load Assumptions Total system weight 888.1 Ibs Wind exposure B Weight/attachment 31.7 Ibs Wind speed 109 mph Racking weight 112.1 Ibs Ground snow load 50 psf Distributed weight 2.6 psf Attachment spacing portrait 4.0' Site Elevation 889.0 ft SDS 0.051 Roof Information Roof Material Family Comp Shingle Roof material Comp Shingle Building height 15 ft Roof attachment Flashfoot2 Staggered attachments No Roof slope 14° Attachment hardware Square Risk category II Roof shape Gable Specific gravity 0.42 Las[updated by—pmi,—ki,hbff o,11ID6123 1D'.31 AM Page 1 bf 7 smar By Us_safdarAli Haider)( —o,,) ZMk IRONRIDGE pitched— 23357 INDUSTRIAL BLw.,HAY—D,CA saws Span Details XR100 - Portrait Module Max Max Zone Position span cantilever Zone 1/2e Normal 6' 2'5" Exposed 6' 2'5" Edge 6' 2'5" Zone 2n/2r/3e Normal 6' 2'5" Exposed 6' 2'5" Edge 6' 2'5" Zone 3r Normal 6' 2'5" Exposed 6' 2'5" Edge 5'T 2'3" Reaction Forces XR100 - Portrait Module Uplift Down Uplift Lateral Lateral Zone Position (PSF) (Ibs) (Ibs) Par(Ibs) Perp(Ibs) Zone 1/2e Normal 13.4 390 168 96 3 Exposed 20.1 390 264 96 3 Edge 31.8 390 378 96 3 Zone 2n/2r/3e Normal 17.4 390 252 96 3 Exposed 26.1 390 390 96 3 Edge 41.3 390 553 96 3 Zone 3r Normal 20.7 390 306 96 3 Exposed 31.1 390 471 96 3 Edge 49.1 390 667 96 3 Last updated by Benlamin—kinhbff on 11ID612310'.31 AM Page 2 bf smar By Us_safdarAli Haider)c*11>180>I ZMk IRONRIDGE pitched— 23357 INDUSTRIAL BLw.,HAY—D,CA saws Roof Section 1 Details Weights Panels: 16 Provided rail: 112'[8 x 168"] Total weight:888.1 Ibs Rail orientation: East-West Attachments:28 Weight(attachment:31.7 Ibs Panel orientation: Portrait Splices:4 Total Area:343.8 sq ft Entry type:Graphical Clamps:36 Distributed weight:2.6 psf Diagram CV r-I 27' 10" Segments Identifier Columns Row length Rail length Cantilever Rail Attachments Splices Clamps A 8 27'10" 27'10" 1'11" 56'[4 x 168"] 14 2 18 Row segment totals(x 2) 112'[8 x 168"] 28 4 36 Last updated by Benlamin Fe&hbff on 11ID6123 1D'.31 AM Page 3 bf solar By Us_SardarAli Hawed(s11.52e05) AMk IRONRIDGE pitched— 28357 INDUSTRIAL BLw.,HAY—D,CA saws Side View(portrait) 14' PV MODULE RAIL FLASI110012 LI ROOFMEMBRANE BUILDING STRUCTURE Front View(portrait) 4.0' PV MODULE RAIL FLASBFOOT2 ROOF MEMBRANE BUILDING STRUCTURE Last updated by Benlamin—kinhbff on 11ID61231D'.31 AM Page 4 m Smar By Us_SardarAli Haider)c*11>180>I AMk IRONRIDGE pitched mot 23357 INDUSTRIAL BLw.,HAY-D,CA saws Splice Details TOP-FACING SLOT XR100 RAIL INTERNAL SPLICE - BONDING SPRING -XR100 INTERNAL SPLICE Splice Connection SIDE-FACING SLOT XR100 Clamp Detail PV MODULE UNIVERSAL RAIL STOPPER FRAME FASTENING 1„ 1„ SLEEVE OBJECT PV MODULE FRAME UNIVERSAL ----- UNIVERSAL FASTENING -------- FASTENING PV MODULE OBJECT -_-------- _ OBJECT FRAME UNIVERSAL FASTENING RAIL OBJECT RAIL STOPPER PV MODULE SLEEVE FRAME Mid Clamp,Plan Mid Clamp,Front End Clamp,Plan End Clamp,Front FlashFoot2 Detail 8" 14 3, 4 33„ 3„ 1 l8 8 J� 12" d 1„ 4 O Oa Plan View Side View Perspective View Front View Last updated by Benlamin Ferkinhoff on 11ID612310'.31 AM Page 5 m smar By Us_SafdarAli Hawed is —o,,) AMk IRONRIDGE pitched mot 28357 INDUSTRIAL BLw.,HAY-D,CA saws Grounding Diagram - - - - - - - - - - - - - - - - - - - - - - - - - - O - - - - - - - - - - - - - - - - - - - - - - - o 1 I - - - - - - - - - - � — - - n - - - - - - ` - - — — — — — OUFO Clamp • Grounding Lug Fault Current Ground Path Min 10 AWG Copper Wire m Bonded Splice (Rail Connection) *Grounding Lugs and Wire are not required in systems using Enphase microinverters. Last updated by l3enlamin Ferkinhoff on 11ID612310'.31 AM Page 6 m Smar By Us_SafdarAli Haider)c*11>180>I ZMk IRONRIDGE pitched— 28357 INDUSTRIAL BLw.,HAY—D,CA saws Bill of Materials Part Spares Total Qty Rails&Splices XR-100-168B 0 8 XR100,Rail 168"Black XR100-BOSS-01-M1 0 4 Bonded Splice,XR100 Clamps&Grounding UFO-CL-01-B1 0 36 Universal Module Clamp,Black UFO-STP-32MM-B1 0 8 Stopper Sleeve,32MM,Black XR-LUG-03-Al 0 2 Grounding Lug,Low Profile Attachments FF2-02-B2 0 28 FlashFoot2,Black BHW-SQ-02-Al 0 28 Square-Bolt Bonding Hardware Accessories 29-4000-077 0 2 Wire Clips,Molded PVC Black,Polybag 20 XR-100-CAP 0 1 Kit,End Cap XR100(10 sets per bag) BHW-M I-01-A1 0 16 Microinverter/MLPE Bonding Hardware,T-Bolt Last updated by l3enlamin Ferkinhbff on 11ID61231D'.31 AM Page 7 m . ilr PRE-INSTALLATION ATTACHMENTS ❑ Verify module compatibility. See Page 21 for info. COMPOSITION SHINGLE TOOLS REQUIRED ❑ Cordless Drill(non-impact) ❑ 3/8"Socket ❑ Impact Driver(for lag bolts) ❑ 1/8"Drill Bit \�J ❑ Torque Wrench(0-250 in-Ibs) ❑ 1/4"Drill Bit FlashFoot2 FlashVue QM L-Mount ❑ 7/16"Socket ❑ T30 Bit ❑ 1/2"Socket ❑ Channel Lock Pliers ❑ 9/16"Socket ❑ #3 Phillips Bit < > < ct> ❑ 7/32"Drill Bit ❑ 3/16"Hex Bit QM QBase QM Classic Comp HUG Mount (Halo UltraGrip) BONDING HARDWARE TORQUE VALUES TILE Please refer to each attachment's individual section for full details on all torque values and instructions. ❑ 3/8"Bonding Hardware Nuts(7/16"Socket):250 in-Ibs Knockout Tile QM Tile Replacement All Tile Hook and ❑ All Tile Hook Carriage Bolts(7/16"Socket): 132 in-Ibs Flashing(optional) ❑ Flat Roof Attachment Nuts(9/16"Socket):250 in-Ibs ❑ Lynx Set Screw(3/16"Hex Drive): 150 in-Ibs > <i> ;> ❑ Lynx Flange Nut(1/2"Socket): 150 in-Ibs QM Quick Hook and QM QBase Tile QM Tile Conduit Flashing(optional) Penetration ADDITIONAL ROOF TYPES < > < > QM Qbase Shake- QM Classic Mount QM Lynx Metal Roof Slate-Metal Shingle Shake Attachment LOW SLOPE ROOF so OQ(7 V�K MOUN�� If using previous version of Integrated Grounding Mid Clamps, Flat Roof Attachment QM QBase Mount End Clamps,Expansion Joints and for a list of approved 3rd party components please refer to Alternate Components Addendum (Version 1.9) o -• . • FLUSH MOUNTINSTALLATION COMPONENTS ilr PRE-INSTALLATION COMPONENTS ❑ Verify module compatibility. See Page 21 for info. TOOLS REQUIRED ❑ Cordless Drill(non-impact) ❑ 1/8"Drill bit ❑ Impact Driver(for lag bolts) ❑ 1/4"Drill bit XR Rail Wire Clip BOSS ❑ Torque Wrench(0-250 in-Ibs) ❑ T30 Torx Bit _rTi-, ❑ 7/16"Socket ❑ Channel Lock Pliers , ❑ 1/2"Socket ❑ #3 Phillips Bit ❑ 9/16"Socket ❑ Paddle Bit UFO and Stopper Ironridge L-Foot and ❑ 7/32"Drill bit Sleeve(30-46MM) CAMO QM L-Foot BONDING HARDWARE TORQUE VALUES Int Please refer to each attachment's individual section for full details -�, o on all torque values and instructions. d End Cap Rail Grounding Lug Module Grounding ❑ Universal Fastening Object(7/16"Socket):80 in-Ibs Lug ❑ Rail Grounding Lug Nut(7/16"Socket):80 in-Ibs ❑ Module Grounding Lug ❑ Grounding Nut(7/16"Socket):60 in-Ibs ❑ Grounding Lug Terminal Screws(7/16"Socket):20 in-Ibs 3/8"Bonding 8"Bonding Jumper ❑ Microinverter Kit Nuts(7/16"Socket):80 in-Ibs Microinverter Kit Hardware Single Use Only ❑ Frameless Module Kit Nuts(7/16"Socket):80 in-Ibs ❑ 3/8"Bonding Hardware Nuts(7/16"Socket):250 in-Ibs ❑ Contour Clamp(T-30 Torx Bit):80 in-Ibs QM Classic Conduit JAYBOX QM Composition Comp Mount Conduit Penetration QM Tile Conduit Frameless Frameless Module Kit Mount End/Mid Clamp Unless otherwise noted,all components have been evaluated for multiple use.They can be uninstalled and reinstalled in the same or new location. Contour Trim Contour Clamp o -• . • FLUSH MOUNTINSTALLATION Gable Roof Flush Mount System Span Table(inches)-Portrait or Landscape Installation Max Module Length:80", Max Module SF:24 SF Of Exposure B Wind Ground Snow:0 psf 10 psf 20 psf 30 psf 40 psf 50 psf 60 psf 70 psf* 80 psf* 90 psf* 100 psf* 110 psf* 120 psf* Exposed Mod. Edge Mod. Speed Slope (mph) (deg.) Group 1 Group 2 Group 3 Group 1 Group 2 Group 3 Group 1 Group 2 Group 3 Group 1 Group 2 Group 3 Group 1 Group 2 Group 3 Group 1 Group 2 Group 3 Group 1 Group 2 Group 3 Group 1 Group 2 Group 3 Group 1 Group 2 Group 3 Group 1 Group 2 Group 3 Group 1 Group 2 Group 3 Group 1 Group 2 Group 3 Group 1 Group 2 Group 3 Group 1 Group 2 Group 3 Group 1 Group 2 Group 3 90 8-20 123 123 123 102 102 102 86 86 86 84 84 84 75 75 75 68 68 68 64 64 64 58 58 58 55 55 55 52 52 52 49 49 49 48 48 48 45 45 45 124 120 107 106 87 79 mph 21-27 121 121 121 99 99 99 84 84 84 83 83 83 76 76 76 69 69 69 64 64 64 59 59 59 56 56 56 53 53 53 50 50 50 48 48 48 48 48 48 121 121 121 113 96 88 28-45 117 117 117 98 98 98 83 83 83 82 82 82 76 76 76 72 72 72 67 67 67 64 64 64 59 59 59 56 56 56 53 53 53 51 51 51 49 49 49 117 117 117 110 99 90 95 8-20 123 123 123 102 102 102 86 86 86 84 84 84 75 75 75 68 68 68 64 64 64 58 58 58 55 55 55 52 52 52 49 49 49 48 48 48 45 45 45 124 112 99 99 82 74 21-27 121 121 121 99 99 99 84 84 84 83 83 83 76 76 76 69 69 69 64 64 64 59 59 59 1 56 56 56 53 53 53 50 50 50 48 48 48 48 48 48 121 120 113 107 88 83 mph 28-45 117 117 117 98 98 98 83 83 83 82 82 82 76 76 76 72 72 72 67 67 67 64 64 64 59 59 59 56 56 56 53 53 53 51 51 51 49 49 49 117 117 110 104 96 85 100 8-20 123 123 122 102 102 102 86 86 86 84 84 84 75 75 75 68 68 68 64 64 64 58 58 58 55 55 55 52 52 52 49 49 49 48 48 48 45 45 45 124 103 92 92 77 72 mph 21-27 121 121 121 99 99 99 84 84 84 83 83 83 76 76 76 69 69 69 64 64 64 59 59 59 56 56 56 53 53 53 50 50 50 48 48 48 48 48 48 121 112 106 101 84 78 28-45 117 117 117 98 98 98 83 83 83 82 82 82 76 76 76 72 72 72 67 67 67 64 64 64 59 59 59 56 56 56 53 53 53 51 51 51 49 49 49 117 117 104 99 90 81 105 8-20 123 123 114 102 102 102 86 86 86 84 84 84 75 75 75 68 68 68 64 64 64 58 58 58 55 55 55 52 52 52 49 49 49 48 48 48 45 45 45 124 97 87 86 73 66 21-271 121 121 121 99 99 99 84 84 84 83 83 83 76 76 76 69 69 69 64 64 64 59 59 59 56 56 56 53 53 53 50 50 50 48 48 48 48 48 48 121 106 99 96 79 74 mph 28-451 117 117 117 98 98 98 83 83 83 82 82 82 76 76 76 72 72 72 67 67 67 64 15111111111111111164 1 59 59 59 56 56 56 53 53 53 51 51 51 49 49 49 117 111 99 96 85 77 110 8-20 123 120 107 102 102 102 86 86 86 84 84 84 75 75 75 68 68 68 64 64 64 58 58 58 55 55 55 52 52 52 49 49 49 48 48 48 45 45 45 119 91 81 81 69 64 mph 21-27 121 121 121 99 99 99 84 84 84 83 83 83 76 76 76 69 69 69 64 64 64 59 59 59 56 56 56 53 53 53 50 50 50 48 48 48 48 48 48 121 99 93 92 76 72 28-45 117 117 117 98 98 98 83 83 83 82 82 82 76 76 76 72 72 72 67 67 67 64 64 64 59 59 59 56 56 56 53 53 53 51 51 51 49 49 49 117 105 96 90 81 73 115 8-20 123 113 101 102 102 101 86 86 86 84 84 84 75 75 75 68 68 68 64 64 64 58 58 58 55 55 55 52 52 52 49 49 49 48 48 48 45 45 45 109 86 76 76 66 59 21-27 121 121 115 99 99 99 84 84 84 83 83 83 76 76 76 69 69 69 64 64 64 59 59 59 56 56 56 53 53 53 50 50 50 48 48 48 48 48 48 117 96 88 87 72 67 mph 28-45 117 117 112 98 98 98 83 83 83 82 82 82 76 76 76 72 72 72 67 67 67 64 64 59 59 59 56 56 56 53 53 53 51 51 51 49 49 49 113 100 89 85 78 72 120 8-20 123 107 96 102 102 96 86 86 86 84 84 84 75 75 75 68 68 68 64 64 64 58 58 58 55 55 55 52 52 52 49 49 49 48 48 48 45 45 45 102 81 72 72 64 54 mph 21-27 121 115 109 99 99 99 84 84 84 83 83 83 76 76 76 69 69 69 64 64 64 59 59 59 56 56 56 53 53 53 50 50 50 48 48 48 48 48 48 111 89 83 84 69 64 28-45 117 117 106 98 98 98 83 83 83 82 82 82 76 76 76 72 72 72 67 67 67 64 64 64 59 59 59 56 56 56 53 53 53 51 51 51 49 49 49 108 96 85 81 74 67 130 8-20 123 96 85 102 96 85 86 86 85 84 84 84 75 75 75 68 68 68 64 64 64 58 58 58 55 55 55 52 52 52 49 49 49 48 48 48 45 45 45 90 73 65 67 55 44 21-27 121 104 98 99 99 98 84 84 84 83 83 83 76 76 76 69 69 69 64 64 64 59 59 59 56 56 56 53 53 53 50 50 50 48 48 48 48 48 48 101 80 74 77 64 58 mph 28-45 117 109 98 98 98 98 83 83 83 82 82 82 76 76 76 72 72 72 67 67 67 64 64 59 59 59 56 56 56 53 53 53 51 51 51 49 49 49 98 87 77 75 69 61 140 8-20 110 87 77 102 87 77 86 86 77 84 84 77 75 75 75 68 68 68 64 64 64 58 58 58 55 55 55 52 52 52 49 49 49 48 48 48 45 45 45 78 66 59 64 45 36 mph 21-27 118 96 88 99 96 88 84 84 84 83 83 83 76 76 76 69 69 69 64 64 64 59 59 59 56 56 56 53 53 53 50 50 50 48 48 48 48 48 48 92 73 67 72 58 48 28-45 113 101 90 98 98 90 83 83 83 82 82 82 76 76 76 72 72 72 67 67 67 64 4 59 59 59 56 56 56 53 53 53 51 51 51 49 49 49 90 80 72 69 64 56 150 8 20 98 79 72 98 79 72 86 79 72 84 79 72 75 75 72 68 68 68 64 64 64 58 58 58 55 55 55 52 52 52 49 49 49 48 48 48 45 45 45 72 60 45 57 -- mph 108 87 80 99 87 80 84 84 80 83 83 80 76 76 76 69 69 69 64 64 64 59 59 59 56 56 56 53 53 53 50 50 50 48 48 48 48 48 48 84 67 61 66 48 38 mph 28-45 105 96 83 98 96 83 83 83 83 82 82 82 76 76 76 72 72 72 67 67 67 64 4 59 59 59 56 56 56 53 53 53 51 51 51 49 49 49 82 74 65 64 59 48 160 8 20 88 72 65 88 72 65 86 72 65 84 72 65 75 72 65 68 68 65 64 64 64 58 58 58 55 55 55 52 52 52 49 49 49 48 48 48 45 45 45 66 49 36 50 mph 21-27 100 80 74 99 80 74 84 80 74 83 80 74 76 76 74 69 69 69 64 64 64 59 59 59 56 56 56 53 53 53 50 50 50 48 48 48 48 48 48 78 64 52 64 41 28-45 97 87 77 97 87 77 83 83 77 82 82 77 76 76 76 72 72 72 67 67 67 64 64 JD4 59 59 59 56 56 56 53 53 53 51 51 51 49 49 49 76 69 1 60 59 54 40 170 8-20 80 67 59 80 67 59 80 67 59 80 67 59 75 67 59 68 67 59 64 64 59 58 58 58 55 55 55 52 52 52 49 49 49 48 48 48 45 45 45 64 40 32 44 29 24 21-27 93 74 68 93 74 68 84 74 68 83 74 68 76 74 68 69 69 68 64 64 64 59 59 59 56 56 56 53 53 53 50 50 50 48 48 48 48 48 48 72 55 41 59 35 27 mph 28-45 90 81 72 90 81 72 83 81 72 82 81 72 76 76 72 72 72 72 67 67 67 64 4 59 59 59 56 56 56 53 53 53 51 51 51 49 49 49 72 64 54 54 45 34 175 8 20 77 64 55 77 64 55 77 64 55 77 64 55 75 64 55 68 64 55 64 64 55 58 58 55 55 55 55 52 52 52 49 49 49 48 48 48 45 45 45 60 36 42 27 24 mph 21-27 90 72 65 90 72 65 84 72 65 83 72 65 76 72 65 69 69 65 64 64 64 59 59 59 56 56 56 53 53 53 50 50 50 48 48 48 48 48 48 72 49 37 56 33 26 28-45 87 78 69 87 78 69 83 78 69 82 78 69 76 76 69 72 72 69 66 66 66 64 64 64 59 59 59 56 56 56 53 53 53 51 51 51 49 49 49 67 64 48 49 42 32 180 8-20 73 64 48 73 64 48 73 64 48 73 64 48 73 64 48 68 64 48 64 64 48 58 58 48 55 55 48 52 52 48 49 1 49 48 48 48 48 45 45 45 57 34 28 39 26 21 21-27 87 69 64 87 69 64 84 69 64 83 69 64 76 69 64 69 69 64 64 64 64 59 59 59 56 56 56 53 53 53 50 1 50 50 48 48 48 48 48 48 68 44 33 53 32 24 mph 28-45 84 76 67 84 76 67 83 76 67 81 76 67 75 75 67 72 72 67 66 66 66 64 64 64 59 59 59 56 56 56 53 1 53 53 51 51 51 49 49 49 65 59 44 48 40 30 =min 72"span =min 64"span =min 48"span * =Note:additional installation requirement for CAMO module clamp. See Note 10 on Page 3 for details. REV 02/09/2021 _=Shaded cells indicate conditions in which UFO Mid Clamp connection capacity is exceeded. See Note 9 on page 2 for details. IF - a 11 -�I Notation (Per ASCE 7-16) Grouping of ASCE 7-16 Roof Zones (Gable) 3e; 2n ;3r 0 2n ;3e a = 10% of least horizontal dimension or 0.4h, whichever is smaller, but not less than either 4% of least horizontal dimension or 3 ft (0.9 Roof m). If an overhang exists, the edge distance shall be measured from Slope 80 - 270 280 - 450 e the outside edge of the overhang_ The horizontal dimensions used Group Group Group Group Group Group Ze 2r 2r! ze to compute the edge distance shall not include any overhang Group 1 2 3 1 2 3 h distances. ASCE 1 2n 3r t 2n 3e I a I B= Horizontal dimension of building measured normal to wind 7-16 2e 2r 2e 3r r ELEVATION direction, in ft (m). Roof Zones 3e 2r 3e ©n 3r 3r (2n 3e h = Mean roof height, in ft (m). Figure 2:ASCE Roof Zone Locations for Gable Roofs 0 =Angle of plane of roof from horizontal, in degrees.