HomeMy WebLinkAboutRE_ AMCON FPE AnalysisGood morning Linda, I am generally not inclined to allow a building to be designed under two different sets of codes; however, in this case, it is appropriate. I am approving the use of FM Global standards for the existing warehouse area of AMCON. Given the existing ceiling heights, commodity, and storage heights, and overall conditions, this approach makes sense and better aligns with the actual design criteria of the building. Shelby Wolf Fire Marshal/Assistant Fire Chief City of Fridley Public Safety Department/Fire Division 7071 University Avenue NE Fridley, MN 55432 (763) 572-3621 Shelby.Wolf@Fridleymn.gov <mailto:Shelby.Wolf@Fridleymn.gov> From: Linda French <linda@cw-fg.com> Sent: Tuesday, January 13, 2026 2:34 PM To: Wolf, Shelby <Shelby.Wolf@fridleymn.gov> Subject: AMCON FPE Analysis Shelby, I wanted to follow up with you regarding the FPE Analysis Report that I submitted for the AMCON expansion and existing storage areas. The areas being expanded into were never intended for or designed for the storage of uncartoned expanded plastic commodities and therefore the sprinkler systems need to be designed to meet current code. As the 2016 NFPA 13 does not specifically address the storage of uncartoned expanded plastics, I used 2022 NFPA 13 design criteria based on previous discussions between you and Escape Fire Protection for the expansion areas. The existing storage areas were designed in 2014 to meet the requirements of 2010 NFPA 13 for the storage of exposed expanded plastics up to 15’-0 in height with a 20’-0 ceiling. The exposed expanded plastic commodities being stored and the storage configuration has not changed since the 2014 sprinkler system upgrades were completed. However, it was determined during this analysis that a smoke and heat removal system should have been required in 2014 when the upgrades were made as an ESFR system was not installed. To meet the intent of the 2010 system requirements in 2014, AMCON and Future Foam have agreed to upgrade the existing systems to ESFR systems to eliminate the need for a smoke and heat removal system. After extensive conversations and review with AMCON and Future Foam for the existing areas, it has been determined that major modifications to the existing sprinkler systems installed originally and in 2014 would be required to meet the specified design criteria in the FPE report using the 2022 NFPA 13 requirements. Is the City of Fridley open to the possibility of using FM Global Design Criteria for the existing storage areas? Data Sheet 8-9 provides design criteria in Table 6 for ceiling level protection of Uncartoned Expanded Plastic commodities in solid piles. The design criteria in Data Sheet 8-9, in my opinion, is better suited for the existing building height and storage conditions as the ceiling heights in the existing areas are 18’-0 and 22’-0. The 2022 NFPA 13 Table 23.3.1 only addresses ceiling heights starting at 30’-0 which is considerably different from the existing conditions. I have completed several hydraulic calculations using both the 2022 NFPA 13 criteria as well as the FM Global design criteria and determined the following: 1. The modifications needed to meet the FM Global design criteria would include replacing the existing 11.2K sprinkler heads with 16.8K sprinkler heads. Some modification to the existing sprinkler main and branchline piping may be needed where tree systems are currently installed. This would be verified with hydraulic calculations performed for each system by the contracted sprinkler contractor. 2. The modifications needed to meet the 2022 NFPA 13 design criteria would require all of the sprinkler branchlines with 3/4” outlets to be replaced to facilitate installing the 1” orifice 25.2K sprinkler heads as well as change all of the tree systems into gridded sprinkler systems. I would like to modify the AMCON FPE report to address the expansion storage areas separately from the existing storage areas if you are open to using the FM Global design criteria for the existing storage areas. Please feel free to contact me if you have any questions. Regards, Linda D. French Coastwise Fireguard, Inc. Linda@cw-fg.com <mailto:Linda@cw-fg.com> (651) 248-5148 楏半穕ㅉ楎獉湉ㅧ䍤㙉浉䝆㉡䰱歖橚呌塒橖穚䕗䍎此愵ㅡ䩨呎ㅁ南獉浉灴䍚㙉浉䝆㉡䰱歖橚呌塒橖穚䕗䍎此愵ㅡ䩨呎ㅁ南㥊攮䩹摨兗佩䩩摯剈捷潺䱶串慳噗摵䵈奵㤲婵汭䱮摭奪㕹婶婭奰唲扵噭䰰䥹䥳汭捺䥹䤶桭搰䉈佺㡩捶刳䱺摮扰剭摶䴳扵噭䰰娲婫䩔乨䕪䱹摔婬䵔乴䙄奪こ夵摺䱨䉔奪決䵩噗䵩䩭乩㡓䱩䩃奰兘佩䕪伳兄丱捪䴴䥔䥳㕭婩䥩䴶捔临啄串杺䵸睩婩桘䥷潪乸杺丰捔䵹䅪䰱䩃奨䤳佩䥩䥸睩奩汗䥶潪兩䙗兒捖佶乇兂䙕摂噺扔奫匲䅄刱汄敕䩗丳䙗匴 桄夲噫啶汮呌䥖噹剘剨㥓坋䩇嘵桔佲㥃婹啈坲噖噴䕆戰䉔乗杇啶㥅摪摗娱氲敋噪慑啕啺㕅奋獩戲婄摊桺噄摄捅獩夰搳丵䙫剖丳乪硅慗挳扷䵬她ㅕ剴噄䭭砰乗捈娰瑹敆䩬數䩫奃兖捸桗䵭摇块桬捋摇呬㥫儰䉪剭摈慪桔噪則协䉺䴶〰婷婆婚䙕挳久䵚䈱搱ㅗ扎剄克桪奙剖夶汭剴摫扅㥗慮㥃剩歪乸剗啃剖摲ぺ䤹睩奩ㅗ䥹灪䥢䉮娳䥃䥳䩮奺䥓䥳ㅭ奭䩓䱤䩃捨䉈婰䥃䤶六乺歔婷兗䰲啔她䵪乴䕄䵷ㅩ婨婗䱭䙗婨䥄佹䩔奨䅪奸䥹䥳䙭捷汇奫乗䥹潪䵩䥃䥳剭摬汭婪汗䥫潪 佩啔䴲䕪佷奄奴剪佨こ夰䉪䱩汔䵫奔婴啔乹䅔䴵噔䵨剺䥬睩婩䙭慴硗堵㔲扨啗佩䩩托砲䥭睩婩氲娲㕗扦䙭婴䥓䤶乬婯硗敩䥓䥳汭摫汈䥷潪摩乘捬䥩䥳汭奷剗捫䥩䤶啪䱷䕪䴳㑹䵹啺乵奪䱩䩃奵ㅗ䥬潪噩㤲婳睩啧栲扬䩇䤵睩扩氲䥫潪乩啇奸歔䴵啺乴奄䴳ど丰䕭䰳歔奺䕺佴套娴䉔婩奔她䩗䥬睩扩㔲捷噭塴丳婰䥃䤶䵬䵴こ䰱䥔䱸䕔䴳䥪䴰䕄䵺べ䴳奪乺䕄佸䅔䵴啔伵䕄丳捔丰べ䵸䅪䵺䥓䥳䉮愱兗佩䥩䵸䅄䵺䅪乷奅乷杄伲䵅䥸睩捩摈填嘲挴䥃䤶䵪䴴䕄乸䥓䥳䉮娳 㥆挱睭佩䩩摯剈捷潺䱶搲䱶ㅭ奰䨳捶㤲摭㕃扪〲婶摮慳㕗䱲㥺慳㕗慲兗䴹䥪乹䕄伵䥃䥳䩮䥯潪䵩㕓啂搳剂䙘慩㥖呬ㅩ愵搰婪摗匶乮捬䨳唰嘲捷乭慍䙘啘婫摸灕娳䙄摶㥭塌䩺剂瑗兺䕕䥵睩捩串䥷潪摩乘捬㥬扰䉘捬乮扶䙭愰㥗䥵睩捩氲䥫潪䵩䅄䵸兺奸䔲奴兗串こ夳夲䰱噗佪䥇婴歪夳剗奭噗乭䵔䤲睩捩嘳䥩潪敩䙭噋乖卐䙖捱汖塃刱匰婆創㕭呋到吶䩘䵲兄刴啇吴汅摙兆挱䕖吰䥓䥳剮婰䥃䤶婭婫䩔乨䕪䱹摔婬䵔乴䙄奪こ夵摺䱨䉔奪決䵩噗䵩䩭乩䥓䥳噮慵䙘娱㥖 奵ㅗ䥬潪噩㤲婳乬奁欲婵䩮婰硇敬㕓扴㕩挱䥹䥳噮扷䥩䤶摬扶婇兔乇䱰婭慹剗婳歘扵㑗摵䵘䱩䩃搱歇佩䩩敗汔共ㅹ乏杭奷剕吵婘卆婮婚䘰䥂睩摩噭䥹潪䵩㑓䥷睩摩氲捫䥹圶䩹乩決奭奭娰ぃ婺套䰵兔伲歄佴䕄䴰べ丳䥭佸剔佬啄䴱歄塩睓敩ㅇ塺䘲摪㥆奭儳佩䥩䤱䵄䱩䩃戴乘婦剮䥫潪敩䉔兎砲卨灭契䉺奖捘剷䈱呵䩬扆䙈扊欱挲し噴桄䵐䉬呭捺挰䉖捳䨰坫㕅坳桖䵏硅啘灮坩ぅ䱩䩃戴乘慦剗婹睗佩䥩乸䅩䥸睩敩ㅇ塺丳失㥬奭儳佩䥩䥺䥄晩⹑䍙昷䡤摵㥪湟㥺彸獃 䕯畕積潅䐴䕏捖扪敱啌灒す灟䥕㥭乣夲䉯䍰㑸㝎唶桕㥒晋⵨癧䈷㕋⵪夲橍䍅祏匵㕩捣䘱䍶偟倴畣䱃㜷啎䉐㡭婁睈剋㥕杵兹つ块ⴹ㍵䕢䌲浆㈵歅晰洶偶㥲瑪⵹䬶砭摔䄷ⵯ乴䰸䵐䉷ぱ䝄㕦䔰㡴䄳ふ䕘婓晧戶歋䥤㥱元㉖䵆㜳㑩浫祫杹䑙䑙彏䅲婇㕒敇戸䭪兂摫潄奫こⴴ奥桡兪杫ㅇ䡑塍䵤ご㑲䩔呋䩎杺呈坶䍌奰欲牖汭漸慉㥋啲桍氰吶潒㠳托楐婙ⵟ扲潩獆楇䄰発䈱祦婍䩑㉑慘捕朲Ⱒ猢獥楳湯歟祥牟汯楬杮摟瑡≥∺∰∬慴杲瑥㨢栢瑴獰⼺振楬湥獴挮湯楦⹧捧⹣景楦 散渮瑥⼯獵牥楟灭牥潳慮楴湯栠瑴獰⼺振楬湥獴挮湯楦⹧捧⹣景楦散渮瑥⼯搮晥畡瑬索∬瑨灴㩳⼯敭獳条湩⹧湥慧敧敭瑮漮晦捩⹥潣⽭⼪獵牥楟灭牥潳慮楴湯栠瑴獰⼺洯獥慳楧杮攮杮条浥湥⹴景楦散挮浯⨯ⸯ敤慦汵≴笺挢捡敨彤瑡㨢ㄢ㠷㔴㠶ㄱ∲∬汣敩瑮楟≤∺㍤㤵攰㙤㔭戲ⴳㄴ㈰愭晥ⵦ慡㉤㤲愲ぢ挱Ⱒ挢敲敤瑮慩彬祴数㨢䄢捣獥味歯湥Ⱒ攢癮物湯敭瑮㨢氢杯湩眮湩潤獷渮瑥Ⱒ攢灸物獥潟≮∺㜱㐸㜵ㄲㄶⰢ攢瑸湥敤彤硥楰敲彳湯㨢ㄢ㠷㔴㠶ㄱ∲∬慦 業祬楟≤∺Ⱒ栢浯彥捡潣湵彴摩㨢㐢ㅥ㥡㌹ⴵ㘴㈷㐭愶ⴷ㌹ㅣ㤭㡦づ敢㈶扡⹥摦㉥㙡㈱㜭敥ⴳㄴ慣㤭㝣ⵡ挰㥣ㅢ扥戲㕢Ⱒ欢摩㨢∢∬牰彴牰瑯捯汯癟牥楳湯㨢∢∬敲污≭∺摦㉥㙡㈱㜭敥ⴳㄴ慣㤭㝣ⵡ挰㥣ㅢ扥戲㕢Ⱒ爢摥物捥彴牵≩∺牵㩮敩晴眺㩧慯瑵㩨⸲㨰潯≢∬敲牦獥彨湯㨢〢Ⱒ爢煥敵瑳摥损慬浩≳∺屻愢捣獥彳潴敫屮㨢屻砢獭损屣㨢屻瘢污敵屳㨢屛䌢ㅐ≜絝絽Ⱒ猢捥敲≴∺祥桊䝢楣楏歊塡楉䍌汊浢楍楏䉊橍㉕け䑊啌周呎祅楉楷㉡歬橉楯䝍獚浖晰 ㍚灂䡔䵤ㅓ癬啑㉳歙呒浔䭊啍ㅰ䡖瑫步佚䙓昹坓畒塡䝒卖獉湉瑨ㅣ漹䙚ㄹ䝤楫楏半䝏㑙啎橸䕎䙰㍔㙖坑昱坤婖止䉆楉楷䝥稱㉘歨㉘桬䍤㙉橉㍅䑏ㅑ橎㑣呍楉兦⸮步煭琹䔹兕偬甶儰畖偯䄲瘮䈸楪婂橧㥃噴䉱摚摺䍊䥅唶業㑐ㅟ䤹䵇水敓祍䡒㐰⵺噅弰婕䤭䩥坖㐸瑂畩䬴坤䵚㥍ⵖ焴㥰內灩獊戵橂㉔甲獮奖㉦扔䥵杳敓㡣ⵘ搳桬㉟䥁䬳䥐敵乫偋㥣瑖䑲瑒㥁ㅹ呙伱㍗ㄶ䵁㙡煃㔭洶湃捸敋䉧畁奉㠭䭪乯扒㥏⵱晄奸噵䙸䭩歺䤴㤰慓券䥭昭剚煌䅨ぁ㐵䍨江灗慪䜹摒㠶㥷㡂 䭕祣當㘳塁坒佦㔵㡱噙穕㥅㍒千樶呬Ů渁빦ࡽ旤翼